1
Shield bus carrier
2
Shield bus (10mm x 3mm)
3
Shield clamp
4
Cable shield
To attach the shield the mounting of shield bus carriers are necessary. The shield bus
carrier (available as accessory) serves to carry the shield bus to connect cable shields.
1.
Each System SLIO 8x periphery module has a carrier hole for the shield bus carrier.
Push the shield bus carrier, until they engage into the module. With a flat mounting
rail for adaptation to a flat mounting rail you may remove the spacer of the shield
bus carrier.
2.
Put your shield bus into the shield bus carrier.
3.
Attach the cables with the accordingly stripped cable screen and fix it by the shield
clamp with the shield bus.
2.6 Demounting
2.6.1 Demounting bus coupler
CAUTION!
Bus interface and power module may not be separated! Here you may
only exchange the electronic module!
1.
Power-off your system.
2.
Remove if exists the wiring of the bus coupler.
3.
For demounting and exchange of a (head) module or a group of
modules, due to mounting reasons you always have to remove the
electronic module right beside. After mounting it may be plugged
again.
Press the unlocking lever at the lower side of the just mounted right module near
the bus coupler and pull it forward.
Shield attachment
Proceeding
System SLIO
Basics and mounting
Demounting > Demounting bus coupler
HB300 | IM | 053-1EC01 | en | 22-30