Error Setting
Index:Sub
Name
Type
Offset
Access Default
Description
0x10F1:00
U8
0
ro
0x0002
Error Setting
0x10F1:01
U32
16
rw
0x0001
n
Local Error Reaction
–
0 = PDO State slave changes the value
of the PDO State Bit (either in the PDO
Parameter or if it is part of the process
data description there. Slave remains in
state
Op
.
–
1 = Disable SyncManager (outputs) from
PDI side and go to ErrSafeOp
0x10F1:02
U16
48
rw
0x0004
n
Sync Error Counter Limit
–
Limit set by the master when slave shall
change its EtherCAT state to
Safe-Op
with AL Status Code 0x1A. The Slave
shall reset an internal error counter when
it is synchronized again and confirms the
state transition from
Safe-Op
to
Op
.
‘Explanation of the elements’ page 82
System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 22-30
84