LED
Description
PWR
green
Bus interface is power supplied
SF
red
n
1 flash per s: With state change due to an error
e.g. a module is removed
n
2 flashes per s: EtherCAT-Timeout (watchdog) e.g.
EtherCAT master is missing
n
Blinking with 2.5Hz: Error in configuration
n
Blinks alternately with MT at firmware update
MT
yellow
Blinks alternately with SF at firmware update
RUN
Off: Bus coupler in state Init
green
Bus coupler in state Operational
green
n
Blinking with 2.5Hz: Bus coupler in state Pre-
Operational
n
SingleFlash: Bus coupler in state Safe-Operational
L/A1
Off: no communication to the preceding station
green
Blinking with 10Hz: Preceding EtherCAT station is con-
nected
L/A2
Off: no communication to the succeeding station
green
Blinking with 10Hz: Succeeding EtherCAT station is
connected
3.3 Address area
Max. number of possible data are 20byte.
Chap. 4.5.2 ‘Accessing the I/O area in the
Address
Bytes
Function
+0
4
Hardware interrupt counter:
number of hardware interrupts
+4
4
Diagnostics interrupt counter:
number of diagnostics interrupts
+8
8
Diagnostic module status
+16
1
Newest Message
available
+17
1
Alignment
+18
1
Error Sync Manager Out
+19
1
Error Sync Manager In
No byte of the output area is used by the EtherCAT coupler.
Status indication
bus interface
Input area
Output area
System SLIO
Hardware description
Address area
HB300 | IM | 053-1EC01 | en | 22-30