Variant 3: Gaps in the target configuration
(1): Target configuration
(2): Actual configuration
Slot
target
Sub-
index
Slot
actual
Mapping I/O
target
FMM
Slot:
2
5
3
4
1
6
1
2
DO DIO AI
DI
DO DIO AI
DI
empty
01
1
00
h
0
0
empty
02
2
00
h
0
0
3
03
3
01
h
0100h
0x
01
000100
4
04
4
02
h
0001h
0x
02
000001
5
05
5
03
h
0101h
0x
03
000101
6
06
6
04
h
0800h
0x
04
000800
Determination of
Mapping
values:
n
Subindex 01: The module of
Slot
target
= 1 is ignored in the actual configuration
à
Mapping = 00h
n
Subindex 02: The module of
Slot
target
= 2 is ignored in the actual configuration
à
Mapping = 00h
n
Subindex 03: The module of
Slot
target
= 3 is in the actual configuration at
Slot
actual
= 1
à
Mapping = 01h
n
Subindex 04: The module of
Slot
target
= 4 is in the actual configuration at
Slot
actual
= 2
à
Mapping = 02h
n
Subindex 05: The module of
Slot
target
= 5 is in the actual configuration at
Slot
actual
= 3
à
Mapping = 03h
n
Subindex 06: The module of
Slot
target
= 6 is in the actual configuration at
Slot
actual
= 4
à
Mapping = 04h
Slot
target
- The FMM configuration always refers to the slot of the target configuration.
Subindex - The subindex for the FMM configuration results from the
Slot
target
. This value
is identical when configuring hardware variants.
Slot
actual
- Slot of the actual configuration on which the module of the target configura-
tion is located.
Mapping - For variant 3
Mapping
corresponds to the hex value of
Slot
actual
i.e. the slot of
the actual configuration on which the module of the target configuration is
located. If modules of the target configuration are to be ignored, the value
00h must be used for
Mapping
.
I/O
target
- Number of input and output bytes of the target configuration. This value is
identical when configuring hardware variants.
FMM
- The value for
FMM
consists of
Mapping
& 00 &
I/O
target
.
The presence of gaps in the System SLIO is not allowed! But you can
place modules and define them via the configuration as empty slot for the
target hardware configuration.
System SLIO
Deployment
Accessing the System SLIO > FMM - Free module mapping
HB300 | IM | 053-1EC01 | en | 22-30
71
Содержание SLIO