SM output parameter
Index:Sub
Name
Type
Offset
Access Default
Description
0x1C32:00
SM output param-
eter
U8
0
ro
32
0x1C32:01
Synchronization
Type
U16
16
rw
n
0x00: Free Run (not synchronized)
n
0x01: Synchronous - synchronized with Sync
Manager Event
n
0x02: DC Sync0 - synchronized with Sync0
Event
n
0x03: DC Sync1 - synchronized with Sync1
Event
0x1C32:02
Cycle time
U32
32
rw
n
Free Run: Time between two local timer
events in ns
n
Free Run: Time between two local timer
events in ns Synchronous SM2 Event: Min-
imum time between two SM2 events in ns
n
DC Sync0: Sync0 Cycle Time (Register
0x9A3-0x9A0) in ns
0x1C32:03
Shift time
U32
64
ro
n
Time between related event and the associ-
ated action (outputs valid hardware)
n
Shift of output valid equal or greater than
0x1C32:09
0x1C32:04
Synchronization
Types supported
U16
96
ro
0x1C32:05
Minimum cycle
time
U32
112
ro
n
Minimum cycle time
supported by the slave
(maximum duration time of the local cycle) in
ns
n
It might be necessary to start the Dynamic
Cycle Time measurement SI04, Bit 14 and
SI08, Bit 0 to get a valid value used in Syn-
chronous or DC Mode
0x1C32:06
Calc and Copy
Time
U32
144
ro
Time needed by the application controller to copy
the process data from the Sync Manager to the
local memory and perform calculations if neces-
sary before the data is sent to the process.
0x1C32:07
Minimum Delay
Time
U32
176
ro
Only important for DC Sync0/1 (Synchronization
type = 0x02 or 0x03): Minimum Hardware delay
time of the slave. Because of software synchroni-
zation there could be a distance between the min-
imum and the maximum delay time.
0x1C32:08
Get Cycle Time
U16
208
ro
n
Bit 0:
–
0: Measurement of local cycle time
stopped
–
1: Measurement of local cycle time
started
If written again, the measured values are reset
Used in Synchronous or (DC Mode with variable
Cycle Time)
n
Bit 1:
–
0: Reserved
–
1: Reset the error counters
n
Bit 15 … 2: Reserved
System SLIO
Deployment
Object Dictionary