9 Input Assemblies (Drive Produces)
76
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
Table 9.9 Error Replies - 158
Error Code
Description
0x02
Invalid Register Number
0x21
Upper/Lower Limit Error
0x22
Write Mode Error
Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done
yet.
Writing
“
Enter
”
when drive is running.
Attempt to write data that is read only.
Attempt to write a parameter when drive is running.
During a CPF06 [Control Circuit Error (EEPROM memory Data Error)] event attempting to write to registers other than
A1-00 [Language Selection], A1-01 [Access Level Selection], A1-02 [Control Method Selection], A1-03 [Initialize
Parameters], A1-04 [Password], A1-05 [Password Setting]
,
E1-03 [V/f Pattern Selection]
,
o2-04 [Drive Model (KVA)
Selection]
.
0x23
Writing Error during Undervoltage
Attempting to write during a drive Uv [Undervoltage] event.
0x24
Writing Error during Parameter Processing
Attempting to write while the drive is storing data.
◆
Dynamic Input Assembly (Vendor Specific Yaskawa Electric (YE) Assy) - 159
(0x9F)
This is a dynamic assembly. You can set the parameters that are used.
Note:
The drive is compatible with option software versions 1111 and later.
Input Instance
Byte
Description
159
0
Configurable Input 1 (Low Byte)
1
Configurable Input 1 (High Byte)
2
Configurable Input 2 (Low Byte)
3
Configurable Input 2 (High Byte)
4
Configurable Input 3 (Low Byte)
5
Configurable Input 3 (High Byte)
6
Configurable Input 4 (Low Byte)
7
Configurable Input 4 (High Byte)
Name
Description
Configurable Input 1
Data read from the MEMOBUS/Modbus address defined in parameter
F6-68 [Dynamic In Assembly 159 Param 1]
. If
F6-
68 = 0
, then MEMOBUS/Modbus address 0x004B (Drive Status) is used.
Configurable Input 2
Data read from the MEMOBUS/Modbus address defined in parameter
F6-69 [Dynamic In Assembly 159 Param 2]
. If
F6-
69 = 0
, then MEMOBUS/Modbus address 0x0041 (Output Frequency) is used.
Configurable Input 3
Data read from the MEMOBUS/Modbus address defined in parameter
F6-70 [Dynamic In Assembly 159 Param 3]
. If
F6-
70 = 0
, then MEMOBUS/Modbus address 0x0026 (Output Current) is used.
Configurable Input 4
Data read from the MEMOBUS/Modbus address defined in parameter
F6-71 [Dynamic In Assembly 159 Param 4]
. If
F6-
71 = 0
, then MEMOBUS/Modbus address 0x0048 (Torque) is used.
◆
3-Wire Control Status2 (Vendor Specific Yaskawa Electric (YE) Assy) - 160
(0xA0)
Input Instance
Byte
Description
160
0
Status Word (Low Byte)
1
Status Word (High Byte)
2
Output Frequency (0.1 Hz) (Low Byte)
3
Output Frequency (0.1 Hz) (High Byte)
Bits
Fields (# bits)
Description
0
Ready
0 = NOT READY
1 = READY
1
Active
0 = NOT RUNNING