9 Input Assemblies (Drive Produces)
70
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
Name
Description
1: Undervoltage
Function Code
MEMOBUS/Modbus Function Code
Refer to
for information.
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
1000-Series, GA500: Multi-Function Digital
Output
GA700, GA800, FP605: Multi-Function Digital
Output 1
1000-Series, GA700, GA800, FP605: Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
GA500: Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
1000-Series, GA500: Multi-Function Photocoupler
1
GA700, GA800, FP605: Multi-Function Digital
Output 2
1000-Series, GA500: Terminal P1
0: P1 OFF
1: P1 ON
GA700, GA800, FP605: Terminal M3/M4
0: M3/M4 OFF
1: M3/M4 ON
1000-Series, GA500: Multi-Function Photocoupler
2
GA700, GA800, FP605: Multi-Function Digital
Output 3
1000-Series, GA500: Terminal P2
0: P2 OFF
1: P2 ON
GA700, GA800: Terminal P1
0: P1 OFF
1: P1 ON
FP605
0: MD/MF OFF
1: MD/MF ON
Multi-Function Digital Output 4
Terminal P2
0: P2 OFF
1: P2 ON
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Units are determined by parameter
o1-03 [Frequency Display Unit Selection]
.
Unit is not affected by Speed Scale SS.
Register Number
MEMOBUS/Modbus Register Number
Register Data
MEMOBUS/Modbus Register Data
*1
Terminals are different for different drive models. Refer to
Terminals that Change depending on the Model of the Drive on page 52
for more information.
*2
Multi-function digital output 4 is not available for 1000-Series, GA500, GA800, or FP605 drives.
Note:
1. This is a paired assembly (105/155).
2. Refer to the MEMOBUS/Modbus Data Table in the drive Technical Manual for a list of monitor data using the MEMOBUS/Modbus
message area.
Table 9.7 Reply Mapping - 155
Function Code
Bits/Byte
Write Success
Read Success
Write Failure
Read Failure
No
Operation
Function Bits (High/Low)
11
11
01
01
00
4
Output Assembly Register
Number (Low Byte)
Output Assembly Register
Number (Low Byte)
Output Assembly Register
Number (Low Byte)
Output Assembly Register
Number (Low Byte)
0
5
Output Assembly Register
Number (High Byte)
Output Assembly Register
Number (High Byte)
Output Assembly Register
Number (High Byte)
Output Assembly Register
Number (High Byte)
0
6
0
Read Data (Low Byte)
Error Code
Error Code
0
7
0
Read Data (High Byte)
0
0
0
Note:
For Error Codes, please refer to
.