YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
11
4
Option Components
◆
Option
A - Connector (CN5)
B - Installation hole
C - LED (MS)
D - LED (NS)
E - Ground terminal (FE) and installation hole
F - Terminal block CN1
G - Option model number
Figure 4.1 Option
*1
Refer to
for more information about the LEDs.
*2
Connect the included ground wire during installation. The ground wire is not necessary for installation on GA700 and GA800 drives.
◆
Terminal block CN1
The communication terminal is a pluggable terminal block that serves as the connection point of the DeviceNet
network communication cable to the option.
Table 4.1 Terminal Descriptions
Terminal
Pin
Color
Signal
Description
1
Black
V-
Network common
2
Blue
CAN_L
CAN data Low
3
-
Shield
Cable shield
4
White
CAN_H
CAN data High
5
Red
V+
Communications network
power DC +24V
◆
Option LED States
The option has two bicolor LEDs:
•
Module status (MS)
•
Network status (NS)
A - 1000-Series, Z1000U
B - GA500, GA700, and GA800
C - FP605
Figure 4.2 Option LED Labels
*1
LED label has transparent background and white letters. Please make sure that you use the correct label for FP605. The LED label for
FP605 drives is packaged with the FP605 drive.
Wait 2 seconds minimum for the power-up diagnostic process to complete before you verify the LED states.
The
shows the operating status of the option LEDs after the power-up diagnostic LED sequence is
complete.
Refer to
for more information about the LEDs.