8 Output Assemblies (Drive Consumes)
42
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
Name
Description
This function is enabled only when
H2-02 = F
.
1000-Series, GA500: Multi-Function Photocoupler
2
GA700, GA800, FP605: Multi-Function Digital
Output 3
1000-Series, GA500: Terminal P2
0: P2 OFF
1: P2 ON
GA700, GA800: Terminal P1
0: P1 OFF
1: P1 ON
FP605
0: MD/MF OFF
1: MD/MF ON
This function is enabled only when
H2-03 = F
.
Multi-Function Digital Output 4
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when
H2-04 = F
.
Speed Reference
Speed Reference
Sets drive speed reference.
Units are determined by parameter
o1-03 [Frequency Display Unit Selection]
.
Unit is not affected by Speed Scale SS.
*1
Terminals are different for different drive models. Refer to
Terminals that Change depending on the Model of the Drive on page 52
for more information.
*2
Multi-function digital output 4 is not available for 1000-Series, GA500, GA800, or FP605 drives.
◆
Standard DI/DO Control (Vendor Specific Yaskawa Electric (YE) Assy) - 107
(0x6B)
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
107
0
Multi-Function
Input 8
Multi-Function
Input 7
Multi-Function
Input 6
Multi-Function
Input 5
Multi-Function
Input 4
Multi-Function
Input 3
Run Rev
Run Fwd
1
-
-
-
-
-
Fault Reset
External Fault
2
-
-
1000-Series,
GA500: Multi-
Function
Photocoupler 2
GA700,
GA800, FP605:
Multi-Function
Digital Output 3
1000-Series,
GA500: Multi-
Function
Photocoupler 1
GA700,
GA800, FP605:
Multi-Function
Digital Output 2
1000-Series,
GA500: Multi-
Function
Digital Output
GA700,
GA800, FP605:
Multi-Function
Digital Output 1
-
-
-
3
-
-
-
-
-
-
-
-
4
Analog Output 1 (Low Byte)
5
Analog Output 1 (High Byte)
6
Speed Reference (Low Byte)
7
Speed Reference (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Multi-Function Input 3
Terminal S3 Function Input
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Multi-Function Input 4
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Multi-Function Input 5
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON