YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
87
Drive Fault Code (Dec.)
(MEMOBUS/Modbus #0080 (Hex.))
DeviceNet Fault Code (Hex.)
Description
32
3210
oH4 [Motor Overheat Fault (PTC Input)]
33
7500
CE [Modbus Communication Error]
34
7500
bUS [Option Communication Error]
37
8321
CF [Control Fault]
38
8313
SvE [Zero Servo Fault]
Note:
This fault is not displayed on GA500 or FP605 drives.
39
9000
EF0 [Option Card External Fault]
40
8000
FbL [PID Feedback Loss]
41
8000
UL3 [Undertorque Detection 1]
42
8000
UL4 [Undertorque Detection 2]
43
8000
oL7 [High Slip Braking Overload]
50
8000
dv1 [Z Pulse Fault]
Note:
This fault is not displayed on GA500 or FP605 drives.
51
8000
dv2 [Z Pulse Noise Fault Detection]
Note:
This fault is not displayed on GA500 or FP605 drives.
52
8000
dv3 [Inversion Detection]
Note:
This fault is not displayed on GA500 or FP605 drives.
53
8000
dv4 [Inversion Prevention Detection]
Note:
This fault is not displayed on GA500 or FP605 drives.
54
8000
LF2 [Output Current Imbalance]
55
8000
STo [Safe Torque OFF]
Note:
When using GA500, GA700, GA800, and FP605 drives,
“
STPo
”
(Motor Step-Out Detected) will be shown.
56
7000
PGoH [Encoder (PG) Hardware Fault]
Note:
This fault is not displayed on GA500 drives.
59
1000
SEr [Speed Search Retries Exceeded]
65
8000
FbH [Excessive PID Feedback]
66
9000
EF1 [External Fault (Terminal S1)]
67
9000
EF2 [External Fault (Terminal S2)]
68
8000
oL5 [Mechanical Weakening Detection 1]
69
8000
UL5 [Mechanical Weakening Detection 2]
70
5000
CoF [Current Offset Fault]
73
8000
dWFL [DriveWorksEZ Fault]
77
5000
voF [Output Voltage Detection Fault]
Note:
This fault is not displayed on GA500 or FP605 drives.
78
7000
rF [Braking Resistor Fault]
79
7000
boL [BrakingTransistor Overload Fault]
-
1000
Other faults