6.4 Alarm Detection
6.4 Alarm Detection
♦ Alarm Codes, Causes, and Possible Solutions
Alarms are drive protection functions that do not necessarily cause the drive to stop. Once the cause o f an alarm is
removed, the drive will return to the same status as before the alarm occurred.
When an alarm has been triggered, the ALM light on the digital operator display blinks and the alarm code display
flashes. If a multi-function output is set for an alarm (H 2-DD = 10), that output terminal will be triggered for certain
alarms.
Refer to Minor Faults and Alarms on page 238
for information on alarm that trigger an alarm output.
Note: I f a m ulti-function output is set to close w hen an alarm occurs (H 2 -D D = 10), it will also close w hen m aintenance periods are
reached, triggering alarms LT-1 through LT-4 (triggered only i f Н 2-СЮ = 2F).
Table 6.9 Alarm Codes, Causes, and Possible Solutions
D i g i t a l O p e r a t o r D i s p l a y
M i n o r F a u l t N a m e
REr
AEr
Communication Option N ode ID Setting Error (CANopen)
Option card node address is outside the acceptable setting range.
C a u s e
P o s s ib le S o l u t i o n s
Station number is set outside the possible setting
range.
Set parameter F6-35 to the proper value if a CANopen option card is used.
D i g i t a l O p e r a t o r D i s p l a y
M i n o r F a u l t N a m e
bb
bb
Baseblock
Drive output interrupted as indicated by an external baseblock signal.
C a u s e
P o s s ib le S o l u t i o n s
External baseblock signal was entered via one o f the
m ulti-function input terminals (S3 to S8).
Check external sequence and baseblock signal input timing.
D i g i t a l O p e r a t o r D i s p l a y
M i n o r F a u l t N a m e
b o i
boL
Braking Transistor Overload
The braking transistor in the drive has been overloaded.
C a u s e
P o s s ib le S o l u t i o n s
The proper braking resistor has not been installed.
Select the optimal braking resistor.
D i g i t a l O p e r a t o r D i s p l a y
M i n o r F a u l t N a m e
bus
bUS
Option Communication Error
• After initial communication was established, the connection was lost.
• A ssign a U p/Dow n command or speed reference to the option card.
C a u s e
P o s s ib le S o l u t i o n s
Connection is broken or master controller stopped
communicating.
• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
Option card is damaged.
If there are no problems w ith the wiring and the fault continues to occur, replace the option card.
The option card is not properly connected to the
drive.
• The connector pins on the option card are not properly lined up with the connector pins on the drive.
• Reinstall the option card.
A data error occurred due to noise.
• Check options available to m inim ize the effects o f noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring.
• Try to reduce noise on the controller side.
• U se surge absorbers on magnetic contactors or other equipment causing the disturbance.
• U se recommended cables or som e other type o f shielded line. Ground the shield to the controller side or on the input power side.
• A ll wiring for comm. devices should be separated from drive input power lines. Install an EMC noise filter to the drive input power.
D i g i t a l O p e r a t o r D i s p l a y
M i n o r F a u l t N a m e
r o t l
L O L L
CALL
Serial Communication Stand By
Communication has not y et been established.
C a u s e
P o s s ib le S o l u t i o n s
Communications wiring is faulty, there is a short
circuit, or something is not connected properly.
• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
Programming error on the master side.
Check communications at start-up and correct programming errors.
Communications circuitry is damaged.
• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Termination resistor setting is incorrect.
A termination resistor must be installed at both ends o f a communication line. Slave drives must have the internal termination resistor
switch set correctly. Place DIP switch S2 to the ON position.
T
.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
253
T
ro
u
b
le
s
h
o
o
ti
n
g
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...