5.3 C: Tuning
■ C4-07: Motor 2 Torque Compensation Gain
Functions for motor 2 in the same way that C4-01 functions for motor 1.
Refer to
C3-01: Slip Compensation Gain on page 147
for details on adjusting this parameter.
No.
Parameter Name
Setting Range
Default
C4-07
Motor 2 Torque Compensation Gain
0.00 to 2.50
1.00
♦ C5: Speed Control Loop
The Speed Control Loop controls the motor speed in CLV and CLV/PM control modes. It adjusts torque reference in
order to minimize the difference between speed reference and actual motor speed.
Torque limits
F ig u r e 5 .1 0 S p e e d C o n tro l B lo c k D ia g ra m
■ Adjusting the Speed Control Loop Parameters
Perform Auto-Tuning and set up all motor data correctly prior to adjusting Speed Control Loop parameters.
Analog output signals should be used to monitor the speed reference after softstarter (U1-16) and the motor speed (U1-
05) when adjusting the Speed Control Loop. Refer to
H4: Multi-Function Analog Outputs on page 186
for details on
setting up analog output functions.
Generally when tuning the Speed Control Loop, first optimize the Speed Control Loop gain, then adjust the integral time
settings. Always make adjustments with the load connected to the motor.
The drive provides three different gain and integral time settings for the speed loop. They are automatically switched
over if the switching speed in parameter C5-07 is set larger than 0% (default: 0% for CLV, 2% for CLV/PM). If no
switching speed is defined (C5-07 = 0) the drive will use one set o f speed loop parameters only (C5-01/02).
However, in order to achieve adequate performance in all sections o f a trip, for the most installations it will be necessary
to use two or all three sets of speed loop settings.
Additional Speed loop settings are provided for Position Lock. Those can be used to prevent rollback especially in
gearless applications.
Also refer to
C5-01, C5-03, C5-13 / C5-02, C5-04, C5-14: Speed Control Loop Proportional Gain 1, 2, 3 / Speed
Control Loop Integral Time 1, 2, 3 on page 151.
Perform the following steps for adjusting Speed Control Loop parameters:
1. Check parameter C5-07 and set a speed loop setting switching point. For CLV/PM the drive is preset to 2%. For
CLV set C5-07 between 8~10%.
2. Start a trip and check for any problems like rollback, vibration, overshoot, etc.
3. Adjust C5-19/20 in order to solve rollback problems During Position Lock right before the motor starts
accelerating. Increase C5-19, then shorten C5-20 if the motor rolls back right after the brake releases. Set them
in the opposite way if vibration occurs. If the rollback can not be eliminated by setting C5-19/10, refer to
parameters S3-01/02 (Position Lock Gains at Start).
4. Adjust C5-03/04 in order to improve the performance at start after Position Lock has been finished. Increase C5-
03, then shorten C5-04 if the speed response is slow. Set them in the opposite way if vibration occurs.
5. Adjust C5-01/02 in order to solve problems that occur at speeds higher than C5-07. Increase C5-01, then
shorten C5-02 if overshoot when reaching the top speed occurs. Set them in the opposite way if vibration
occurs.
6. Adjust C5-13/14 in order to improve the stopping behavior. Increase C5-13, then shorten C5-14 if the landing
accuracy is poor. Adjust them in the opposite way if vibrations occur. If problems can not be resolved by setting
C5-13/14, refer to parameter S3-03 Position Lock Gain at Stop). Note that C5-13/14 settings will not be effective
if the speed reference is set from an analog input.
7. Repeat steps 2 to 6 until the desired riding comfort has been reached. Also refer to
Riding Comfort Related
Problems on page 128.
150
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...