5.5 E: Motor Parameters
■ E5-03: Motor Rated Current
Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current
10 to 200% o f drive rated current
Determined by o2-04
Note: The display resolution depends on the rated output pow er o f the drive. M odels CIMR-LIH2A0018 to 2A 0033 and CIMR-
LIH4A0009 to 4A0018 display values in 0.01 A units, while models CIMR-LIH2A0047 to 2A0415 and CIMR-LIH4A0024 to
4A 0216 display values in 0.1 A units.
■ E5-04: Number of Motor Poles
Sets the number o f motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-04
Number o f Motor Poles
2 to 48
12
■ E5-05: Motor Stator Resistance (Single Phase)
Sets the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance
manually.
No.
Parameter Name
Setting Range
Default
E5-05
Motor Stator Resistance (Single Phase)
0.000 to 65.000 Q
Determined by o2-04
■ E5-06: Motor d-Axis Inductance
Sets the d-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
No.
Parameter Name
Setting Range
Default
E5-06
Motor d-Axis Inductance
0.00 to 600.00 mH
Determined by o2-04
■ E5-07: Motor q-Axis Inductance
Sets the q-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
No.
Parameter Name
Setting Range
Default
E5-07
Motor q-A xis Inductance
0.00 to 600.00 mH
Determined by o2-04
■ E5-09: Motor Induction Voltage Constant 1
Sets the induced peak voltage per phase in units o f 0.1 mV/(rad/s) [electrical angle]. This data can be obtained from
either the motor nameplate or from the motor test report issued by the manufacturer of the motor.
No.
Parameter Name
Setting Range
Default
E5-09
Motor Induction Voltage Constant 1
0.0 to 6500.0 mV/(rad/s)
Determined by o2-04
Note: 1. Set E5-24 to 0 w hen setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger 0P E 08. 0 P E 0 8 will also be triggered if
neither E5-09 nor E5-24 are set to 0.0.
2. This param eter is not reset when the drive is initialized using param eter A1-03.
■ E5-11: Encoder Offset
Sets the offset between the rotor magnetic axis and the Z-pulse of the encoder connected. This parameter is set during
a
Auto-Tuning for PM motors and during Encoder Offset Tuning.
No.
Parameter Name
Setting Range
Default
E5-11
Encoder Offset
-180.0 to 180.0 deg
0.0 deg
■ E5-24: Motor Induction Voltage Constant 2
Sets the induced phase-to-phase rms voltage in units o f 0.1 mV/(r/min) [mechanical angle]. This data can be obtained
from either the motor nameplate or from the motor test report issued by the manufacturer of the motor.
No.
Parameter Name
Setting Range
Default
E5-24
Motor Induction Voltage Constant 2
0.0 to 6500.0 mV/(r/min)
0.0 mv/(r/min)
Note: 1. Set E5-09 to 0.0 when setting E5-24. However, setting both E5-09 and E5-24 to 0.0 will trigger OPE08. OPE08 will also be triggered
if neither E5-09 nor E5-24 are set to 0.0.
2. This param eter is not reset when the drive is initialized using param eter A1-03.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
163
P
a
ra
m
e
te
r
D
e
ta
il
s
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...