5.8 L: Protection Functions
■ L8-77: Oscillation Suppression
If speed oscillations with the same frequency as the output frequency occur with an unloaded motor, parameter L8-77
can be adjusted to suppress these oscillations. While watching the motor speed, increase or decrease L8-77 until the
oscillation disappears.
This parameter rarely requires adjustment.
No.
Name
Setting Range
Default
L8-77
Oscillation Suppression
-1 0 0 to 100
0
■ L8-88: Safe Disable Operation Mode
Determines the operation performed by the drive when the Safe Disable input is activated.
No.
Name
Setting Range
Default
L8-88
Safe D isable Operation Mode
0 or 1
1
Setting 0: Mode 0
Setting 1: Mode 1
When the Safe Disabled Input is triggered, the operator displays and alarm, and the corresponding output terminal will
react as follows:
L8-88
Safe Disable Operation
Selection
Alarm Display during Safety Disable
Alarm Output (И 2-П П = 10)
Drive Ready
(И 2-П П = 6)
0 (mode 0)
Hbb
A L M flashes
ON
OFF
1 (m ode1)
Hbb
A L M flashes
OFF
ON
Ч _
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
203
P
a
ra
m
e
te
r
D
e
ta
il
s
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...