6.4 Setting Up the SERVOPACK
6-35
6
* Always OFF when an NS115 is mounted.
Note: “Same as above” means output signals are disabled or allocated to output terminals SO1 to
SO3 through parameter settings 0 to 3.
Signals are output with OR logic when multiple signals are allocated to the same output circuit. Signals
that are not detected are invalid.
Output Signal Reversal
The following parameter can be used to reverse the signals output on output terminals SO1
to SO3.
Output Signal
Parameter
Description
Number
Setting
Positioning Com-
pleted
(/COIN)
Pn50E.0
0
Disabled (Not used for the output signal on the left.)
1
Outputs the signal on the left from the SO1 (CN1-25 and 26) output terminal.
2
Outputs the signal on the left from the SO2 (CN1-27 and 28) output terminal.
3
Outputs the signal on the left from the SO3 (CN1-29 and 30) output terminal.
Speed Coinci-
dence Detection
(/V-CMP)
Pn50E.1
0 to 3
Same as above
∗
Rotation Detection
(/TGON)
Pn50E.2
0 to 3
Same as above
Servo Ready
(/S-RDY)
Pn50E.3
0 to 3
Same as above
Torque Limit De-
tection
(/CLT)
Pn50F.0
0 to 3
Same as above
Speed Limit De-
tection
(/VLT)
Pn50F.1
0 to 3
Same as above
Brake Interlock
(/BK)
Pn50F.2
0 to 3
Same as above
Warning
(/WARN)
Pn50F.3
0 to 3
Same as above
Near
(/NEAR)
Pn510.0
0 to 3
Same as above
Phase C Detection
(/C-PULS)
Pn510.1
0 to 3
Same as above
Pn512
Output Signal Reversal Settings
Factory
Setting:
0000
Position Control
INFO