10.3 Main Commands and Subcommands
10.3.4 Subcommand Details
10-24
( 3 ) Read User Constant
Description
Reads the specified inverter user constant from the Inverter.
Valid only in MECHATROLINK-II 32-byte mode.
Setting Parameters
Monitoring Parameters
Name
Register No.
Setting Range
Remarks
Subcommand Code
OW
0A
0 to 9
02: Read User Constant
Auxiliary Inverter Constant Number
OW
42
0 to FFFFH
Auxiliary Inverter Constant Number
Size
OW
43
1 to 4
Data type: Word (Enter the size of user con-
stant that read out from the leading user con-
stant number of the auxiliary inverter.)
Name
Register No.
Setting
Range
Remarks
Subcommand Response Code
IW
0A
0 to 9
02: Read User Constant
Subcommand Status
IW
0B
Bit
Bit 0 (Command execution flag)
ON during execu-
tion
Bit 3 (Command error completed
status)
ON when an error
occurs during com-
mand processing.
Bit 8 (Command execution com-
pleted)
ON when command
execution is com-
pleted.
Subcommand Response Status
IW
31
Bit
Refer to Subcommand Response Status of
10.4.3 Moni-
toring Parameter List
.
Auxiliary Inverter User Constant
Number
IW
42
0 to FFFFH
Auxiliary User Constant
Reading Data 1
IW
44
0 to 65535
Auxiliary User Constant
Reading Data 2
IW
45
0 to 65535
Auxiliary User Constant
Reading Data 3
IW
46
0 to 65535
Auxiliary User Constant
Reading Data 4
IW
47
0 to 65535