178
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Model
Terminal
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
mm
Terminal
Screw
Size and
Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
B012
L/L1, N/L2
4
2.5 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
2.5
2.5 - 4
10
M4
1.5 - 1.7
(13.5 - 15)
-, +1
4
2.5 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
B1, B2
2.5
2.5 - 4
10
M4
1.5 - 1.7
(13.5 - 15)
4
2.5 - 6
-
M4
1.2 - 1.5
(10.6 - 13.3)
*1