YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
155
Code
Name
Causes
Possible Solutions
oPE03
Multi-Function Input
Setting Err
The settings for these
parameters do not agree:
•
H1-01 to H1-07 [Terminals
S1 to S8 Function Selection]
•
H7-01 to H7-04 [Virtual
Multi-Function Inputs 1 to 4]
Correct the parameter settings.
The settings for MFDIs overlap.
Note:
This does not include
H1-xx
= 20 to 2F [MFDI Function
Select = External Fault]
and
[Reserved]
.
Set the parameters correctly to prevent
MFDI function overlap.
You did not set these pairs of
MFDI functions to Digital
Inputs (
H1-xx
and
H7-01 to H7-
04
) at the same time:
•
Setting values
10 [Up
Command]
and
11 [Down
Command]
•
Setting values
75 [Up 2
Command]
and
76 [Down 2
Command]
•
Setting values
42 [Run
Command (2-Wire Sequence
2)]
and
43 [FWD/REV (2-
Wire Sequence 2)]
Set the MFDI pairs.
You set a minimum of two of
these MFDI combinations to
Digital Inputs (
H1-xx
and
H7-01
to H7-04
) at the same time:
•
Setting values
10 [Up
Command]
and
11 [Down
Command]
•
Setting values
75 [Up 2
Command]
and
76 [Down 2
Command]
•
Setting value
A [Accel/Decel
Ramp Hold]
•
Setting value
1E [Reference
Sample Hold]
•
Setting values
44 to 46 [Add
Offset Frequency 1 to 3 (d7-
01 to d7-03)]
Remove the function settings that are not
in use.