YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
163
Code
Name
Causes
Possible Solutions
oPE33
Digital Output
Selection Error
These two parameters are set at
the same time:
•
H2-60 ≠ F [Term MA,MB,
MC Secondary Function ≠
Not Used]
•
H2-01 = 1xx [Term MA,MB,
MC Function Selection =
Inverse output of xx]
These two parameters are set at
the same time:
•
H2-63 ≠ F [Terminal P1
Secondary Function ≠ Not
Used]
•
H2-02 = 1xx [Term P1
Function Selection = Inverse
output of xx]
These two parameters are set at
the same time:
•
H2-66 ≠ F [Terminal P2
Secondary Function ≠ Not
Used]
•
H2-03 = 1xx [Term P2
Function Selection = Inverse
output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse
output of xx]
settings.
Note:
If you use the function to output
logical calculation results (
H2-60,
H2-63, H2-66 ≠ F
), you cannot set
H2-01 to H2-03 = 1xx
.
These parameter pairs are set
incorrectly:
•
H2-21 [Comparator 1 Lower
Limit]
>
H2-22 [Comparator
1 Upper Limit]
•
H2-27 [Comparator 2 Lower
Limit]
>
H2-28 [Comparator
2 Upper Limit]
•
Set parameters
H2-21
≤
H2-22
.
•
Set parameters
H2-27
≤
H2-28
.
◆
Auto-Tuning Errors
This table gives information about errors detected during Auto-Tuning. If the drive detects
an Auto-Tuning error, the keypad will show the error and the motor will coast to stop. The
drive will not send notification signals for faults and alarms when Auto-Tuning errors
occur.
Two types of Auto-Tuning errors are:
Endx
and
Erx
.
Endx
identifies that Auto-Tuning has
successfully completed with calculation errors. Find and repair the cause of the error and
do Auto-Tuning again, or set the motor parameters manually. You can use the drive in the
application if you cannot find the cause of the
Endx
error.
Erx
identifies that Auto-Tuning was not successful. Find and repair the cause of the error
and do Auto-Tuning again.