20
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Model
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
(Default)
Maximum
Applicable Motor
Output
kW (HP)
Rated Output
Current
A
Maximum
Applicable Motor
Output
kW (HP)
Rated Output
Current
A
2012
2.2 (3)
11.0
3.0 (4)
12.2
2021
3.7 (5)
17.6
5.5 (5)
21.0
2030
5.5 (7.5)
25.0
7.5 (10)
30
2042
7.5 (10)
33.0
11 (15)
42
2056
11 (15)
47.0
15 (20)
56
2070
15 (20)
60.0
18.5 (25)
70
Table 6.4 Three-Phase AC 400 V Class
Model
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
(Default)
Maximum
Applicable Motor
Output
kW (HP)
Rated Output
Current
A
Maximum
Applicable Motor
Output
kW (HP)
Rated Output
Current
A
4001
0.2 (1/2)
1.2
0.4 (1/2)
1.2
4002
0.4 (3/4)
1.8
0.75 (1)
2.1
4004
0.75 (2)
3.4
1.5 (2)
4.1
4005
1.5 (3)
4.8
2.2 (3)
5.4
4007
2.2 (3)
5.6
3.0 (4)
7.1
4009
3.0 (4)
7.3
3.7 (5)
8.9
4012
3.7 (5)
9.2
5.5 (7.5)
11.9
4018
5.5 (10)
14.8
7.5 (10)
17.5
4023
7.5 (10)
18.0
11 (15)
23.4
4031
11 (15)
24.0
15 (20)
31.0
4038
15 (20)
31.0
18.5 (25)
38.0