14 Drive Control, Duty Modes, and Programming
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
113
No.
(Hex.)
Name
Description
C6-02
(0224)
Carrier Frequency
Selection
Sets the carrier frequency for the transistors in the drive.
1 : 2.0 kHz
2 : 5.0 kHz (4.0 kHz for AOLV/PM)
3 : 8.0 kHz (6.0 kHz for AOLV/PM)
4 : 10.0 kHz (8.0 kHz for AOLV/PM)
5 : 12.5 kHz (10.0 kHz for AOLV/PM)
6 : 15.0 kHz (12.0 kHz AOLV/PM)
7 : Swing PWM4 (Audible Sound 1)
8 : Swing PWM4 (Audible Sound 2)
9 : Swing PWM4 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
B : Leakage Current Rejection PWM
F : User Defined (C6-03 to C6-05)
d1-01 - d1-
16
(0280 -
0291)
RUN
Reference 1 to 16
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection
.
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from
o1-03 [Frequency
Display Unit Selection]
. Set
H1-xx = 6 [MFDI Function Select = Jog
Reference Selection]
to use the Jog frequency reference.
d2-01
(0289)
Frequency Reference
Upper Limit
Sets maximum limit for all frequency references. The maximum output
frequency is 100%.
d2-02
(028A)
Frequency Reference
Lower Limit
Sets minimum limit for all frequency references. The maximum output
frequency is 100%.
E1-01
(0300)
Input AC Supply
Voltage
Sets the drive input voltage.
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
E1-05
(0304)
Maximum Output
Voltage
Sets the maximum output voltage for the V/f pattern.
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV