E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
E2-01
(030E)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
E2-11
(0318)
Motor Rated Power
Sets the motor rated output in the units from
o1-58 [Motor Power Unit
Selection]
.
H1-01 - H1-
07
(0438, 0439,
0400 - 0404)
Terminal S1 to S7
Function Selection
Sets the function for MFDO terminals S1 to S7.
H2-01
(040B)
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
H2-02
(040C)
Term P1-C1
Function Selection
Sets the function for MFDO terminal P1-C1.
H2-03
(040D)
Term P2-C2
Function Selection
Sets the function for MFDO terminal P2-C2.
H3-01
(0410)
Terminal A1 Signal
Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
4 : -10 to +10V (Bipolar Reference)
H3-02
(0434)
Terminal A1
Function Selection
Sets the function for MFAI terminal A1.
H3-03
(0411)
RUN
Terminal A1 Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A1.
H3-04
(0412)
RUN
Terminal A1 Bias
Setting
Sets the bias of the analog signal input to MFAI terminal A1.
H3-09
(0417)
Terminal A2 Signal
Level Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
4 : -10 to +10V (Bipolar Reference)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV