TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Code
Name
Causes
Possible Solutions
b1-01 = 3 [Frequency
Reference Selection 1 = Option
PCB]
is set, but there is no
option card connected to the
drive.
b1-02 = 3 [Run Command
Selection 1 = Option PCB]
is
set, but there is no option card
connected to the drive.
Connect an option card to the drive.
These parameters are set at the
same time:
•
b1-01 = 4 [Pulse Train
Input]
•
H6-01 ≠ 0 [Terminal RP
Pulse Train Function ≠
Frequency Reference]
Set
H6-01 = 0
.
oPE07
Analog Input
Selection Error
The settings for
H3-02 and H3-
10 [MFAI Function Select]
and
H7-30 [Virtual Analog Input
Selection]
overlap.
Set
H3-02, H3-10, and H7-30
correctly
to prevent overlap.
Note:
It is possible to set these functions to
multiple analog input terminals at the
same time:
•
Setting value
0 [Frequency
Reference]
•
Setting values
F and 1F [Not Used]