YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
57
•
After you connect the wires to the terminal block, lightly pull on the wires to make sure
that they do not come out of the terminals.
•
Do not let strain on the wiring cause damage. Use a strain relief near the wiring to
release the tension. Refer to
for an example.
A - Cable clamp
Figure 10.4 Strain Relief Example
Table 10.1 Recommended Wiring Tools
Screw
Size
Screw
Shape
Wire
Gauge
Adapter
Bit
Torque
Driver Model
(Tightening
Torque)
Torque
Wrench
(Tightening
Torque)
Model
Manufac
turer
M3
-
Bit
SF-BIT-SL
0,5X3,0-70
PHOENIX
CONTACT
TSD-M
1,2NM
(0.3 - 1.2 N∙m
(2.7 - 10.6
lbf∙in))
-
M4
-
Bit
SF-BIT-SL
1,0X4,0-70
PHOENIX
CONTACT
TSD-M 3NM
(1.2 - 3.0 N∙m
(10.6 - 26.6
lbf∙in))
-
M5
≤ 25 mm
2
(AWG
10)
Bit
SF-BIT-SL
1,2X6,5-70
PHOENIX
CONTACT
TSD-M 3NM
(1.2 - 3.0 N∙m
(10.6 - 26.6
lbf∙in))
-
≥ 30 mm
2
(AWG 8)
-
4.1 - 4.5 N∙m
(36.3 - 39.8
lbf∙in)
M6
(WAF: 5
mm)
-
Bit
SF-BIT-HEX
5-50
PHOENIX
CONTACT
-
5 - 9 N∙m
(44.3 - 79.7
lbf∙in)
*1