TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
91
Table 11.2 Input Data for Induction Motor Auto-Tuning
Input Data
Parameter
Unit
Auto-Tuning Mode
(T1-01 Setting)
Rotational
Auto-Tuning
(0)
Stationary
Auto-Tuning 1
(1)
Stationary
Line-Line
Resistance
(2)
Motor Rated
Power
T1-02
kW
x
x
x
Motor Rated
Voltage
T1-03
V
x
x
-
Motor Rated
Current
T1-04
A
x
x
x
Motor Base
Frequency
T1-05
Hz
x
x
-
Number of
Motor Poles
T1-06
-
x
x
-
Motor Base
Speed
T1-07
min
-1
x
x
-
Motor No-Load
Current
T1-09
A
-
x
-
Motor Rated Slip
Frequency
T1-10
Hz
-
x
-
Motor Iron Loss
T1-11
W
x
-
-
Test Mode
Selection
T1-12
-
-
x
-
No-Load Voltage
T1-13
V
x
x
-
*1
Shows 0 Hz as the default value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0
Hz.
*2
Input this value when
A1-02 = 0 [Control Method Selection = V/f]
.
*3
If
T1-12 = 1 [Test Mode Selection = Yes]
, when you run the motor in Drive Mode for the first time after
Auto-Tuning, the drive will automatically set
E2-02 [Motor Rated Slip]
and
E2-03 [Motor No-Load
Current]
.
*4
Input this value when
T1-10 [Motor Rated Slip Frequency] = 0 Hz
.
*5
Set the same value to No-Load Voltage as
T1-03 [Motor Rated Voltage]
to get the same characteristics
using Yaskawa 1000-Series drives or other legacy models.