H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
Description
Control
Mode
Pg.
V/
f
O
L
V
P
M
17
Torque Detection 1 (N.C.)
Open: When the output current/torque exceeds the value set in parameter L6-02 for more
time than is set in parameter L6-03.
O O O
18
Torque Detection 2 (N.O.)
Closed: When the output current/torque exceeds the value set in parameter L6-05 for
more time than is set in parameter L6-06.
O O O
19
Torque Detection 2 (N.C.)
Open: Output current/torque exceeds the value set in parameter L6-05 for more time
than is set in parameter L6-06.
O O O
1A
Reverse Direction
Closed: Drive is running in the reverse direction.
O O O
1B
During Baseblock (N.C.)
Open: Drive is in Baseblock condition. Output is disabled.
O O O
1C
Motor 2 Selection
Closed: Motor 2 is selected by a digital input (H1-
oo
= 16)
O O −
1E
Restart Enabled
Closed: An automatic restart is performed
O O O
1F
Overload Alarm oL1
Closed: oL1 is at 90% of its trip point or greater.
O O O
20
oH Pre alarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
O O O
22
Mechanical Weakening
(N.O.)
Closed: Mechanical Weakening detected.
O O O
2F
<1>
Maintenance Period
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may
require maintenance.
O O O
30
During Torque Limit
Closed: When the torque limit has been reached.
− O −
37
During Frequency Output
Open: No frequency output from drive if stopped, with baseblock, with DC injection
braking during initial excitation, or with short-circuit braking.
Closed: Drive is outputting a frequency
O O O
38
Drive Enable
Closed: Multi-function input closes (H1-
oo
= 6A)
O O O
39
Watt Hour Pulse Output
Output units are determined by H2-06, outputs 200 ms pulse for each incremented kWh
count.
O O O
3C
LOCAL/REMOTE Status
Closed: LOCAL
Open: REMOTE
O O O
3D
Speed Search
Closed: Speed search is being executed.
O O O
3E
PID Feedback Loss Low
Closed: PID Feedback Loss Low.
PID feedback value is below the level set to
b5-13 for longer than the time set in b5-14. O O O
3F
PID Feedback Loss High
Closed: PID Feedback Loss High.
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37. O O O
4A
KEB Operation
Closed: KEB is being performed.
O O O
4B
Short-Circuit Brake
Closed: Short-Circuit Braking is active.
−
− O
4C
During Fast-stop
Closed: Fast-stop command is entered
O O O
4D
oH Pre-alarm Time Limit
Closed: oH Pre-alarm time limit is passed.
O O O
4E
<1>
Braking Transistor Fault (rr)
Closed: The built-in dynamic braking transistor failed.
O O O
4F
<1>
Braking Resistor Overheat
(oH)
Closed: The dynamic braking resistor has overheated.
O O O
90 to 92
DWEZ Digital Outputs 1 to 3
Reserved for DWEZ digital output functions.
O O O
100 to 192
H2 Parameter Functions
Reversed Output Switching of
0 to 92
Reverse the output switching of the multi-function output functions. Set the last two
digits of 1
oo
to reverse the output signal of that specific function.
Examples:
Setting “108” reverses the output of “During baseblock,” which is setting value 08.
Setting “14A” reverses the output of “During KEB operation”, which is setting “4A”.
O O O
<1> Available in drive software versions PRG: 1016 and later.