n
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred.
Branch circuit protection shall be provided by any of the following according to
• Non-time Delay Class J, T, or CC fuses.
• Time Delay Class J, T, CC, or RK5 fuses.
• Semiconductor fuses.
• Molded Case Circuit Breakers (MCCB).
Table D.10 Factory Recommended Drive Branch Circuit Protection
Drive Model
Non-time Delay
Fuse Rating (A)
<1>
Time Delay Fuses
Bussmann
Semiconductor
Fuse Part Number
(Fuse Ampere)
<4>
MCCB
<5>
Class J, T, or CC
Fuse Rating (A)
<2>
Class RK5
Fuse Rating (A)
<3>
Rating (A)
Minimum
Enclosure
Volume (in
3
)
200 V Class Single-Phase Drives
BA0001
6
3.5
4
FWH-25A14F (25)
15
600
BA0002
10
6
8
FWH-25A14F (25)
15
600
BA0003
20
10
15
FWH-60B (60)
15
600
BA0006
40
20
30
FWH-80B (80)
30
1152
BA0010
40
35
45
FWH-100B (100)
50
1152
BA0012
50
40
50
FWH-125B (125)
60
1152
BA0018
80
60
70
FWH-175B (175)
80
1152
200 V Class Three-Phase Drives
2A0001
3
1.5
2
FWH-25A14F (25)
15
600
2A0002
6
<6>
3
3
FWH-25A14F (25)
15
600
2A0004
15
<7>
6
8
FWH-25A14F (25)
15
600
2A0006
20
10
15
FWH-25A14F (25)
15
1152
2A0010
25
15
20
FWH-70B (70)
25
1152
2A0012
25
20
30
FWH-70B (70)
30
1152
2A0020
40
40
50
FWH-90B (90)
60
1152
2A0030
–
60
80
FWH-100B (100)
90
1152
2A0040
–
90
110
FWH-200B (200)
125
1152
2A0056
–
110
150
FWH-200B (200)
150
2560
2A0069
–
125
175
FWH-200B (200)
200
2560
400 V Class Three-Phase Drives
4A0001
3
2
2
FWH-40B (40)
15
1152
4A0002
6
3.5
3
FWH-40B (40)
15
1152
4A0004
15
<7>
7
8
FWH-50B (50)
15
1152
4A0005
20
<8>
10
10
FWH-70B (70)
15
1152
4A0007
25
<9>
12
15
FWH-70B (70)
20
1152
4A0009
25
15
20
FWH-90B (90)
20
1152
4A0011
30
20
30
FWH-90B (90)
35
1152
4A0018
–
35
45
FWH-80B (80)
50
1152
4A0023
–
40
50
FWH-100B (100)
60
1152
4A0031
–
60
80
FWH-125B (125)
90
1152
4A0038
–
70
90
FWH-200B (200)
110
1152
<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004, 4A0004, 4A0005, and 4A0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.
<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
D.3 UL and CSA Standards
478