3.10 MEMOBUS/Modbus Termination
The two ends of the MEMOBUS/Modbus network line must be terminated. The drive has a built-in termination resistor that
can be enabled or disabled using DIP switch S2. If a drive is a single drive on the network or is located at the end of a network
line, set DIP switch S2 to the ON position to enable the termination resistor. Disable the termination resistor on all slave drives
that are not located at the network line end.
Table 3.15 MEMOBUS/Modbus Switch Settings
S2 Position
Description
ON
Internal termination resistor ON
OFF
Internal termination resistor OFF (no termination resistor); default setting
DIP Switch S2
OFF ON
Figure 3.27 DIP Switch S2
Note:
Refer to the MEMOBUS/Modbus communications manual for details on MEMOBUS/Modbus.
3.10 MEMOBUS/Modbus Termination
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
71
3
Electrical Installation