L6-08
Mechanical Weakening
(oL5) Detection Operation
This function can detect an over/undertorque in a certain speed
range as a result of machine fatigue. It is triggered by a certain
operation time and uses the oL1 detection settings (L6-01 to
L6-02)
0: Mechanical Weakening Detection disabled.
1: Continue running (alarm only). Detected when the speed
(signed) is greater than L6-09.
2: Continue running (alarm only). Detected when the speed
(not signed) is greater than L6-09.
3: Interrupt drive output (fault). Detected when the speed
(signed) is greater than L6-09.
4: Interrupt drive output (fault). Detected when the speed (not
signed) is greater than L6-09.
5: Continue running (alarm only). Detected when the speed
(signed) is less than L6-09.
6: Continue running (alarm only). Detected when the speed
(not signed) is less than L6-09.
7: Interrupt drive output (fault). Detected when the speed
(signed) is less than L6-09.
8: Interrupt drive output (fault). Detected when the speed (not
signed) is less than L6-09.
0 to 8
0
A A A
468
L6-09
Mechanical Weakening
Detection Speed Level
Sets the speed that triggers mechanical weakening detection.
When L6-08 is set for an unsigned value, the absolute value is
used even if the setting is negative.
-110.0 to
+110.0% 110% A A A
469
L6-10
Mechanical Weakening
Detection Time
Sets the time a mechanical weakening has to be detected before
an Alarm/Fault is triggered.
0.0 to 10.0
s
0.1 s A A A
46A
L6-11
Mechanical Weakening
Detection Start Time
Sets the operation time (U1-04) that has to be passed before
Mechanical weakening detection is active.
0 to 65535
0
A A A
46B
L7: Torque Limit
Use L7 parameters to configure the torque limit function.
L7-01
Forward Torque Limit
Sets the torque limit value as a percentage of the motor rated
torque. Four individual quadrants can be set.
L7-01
L7-03
L7-02
L7-04
output torque
positive torque
REV
negative torque
FWD
motor
r/min
regeneration
regeneration
0 to 300 200% − A −
4A7
L7-02
Reverse Torque Limit
0 to 300 200% − A −
4A8
L7-03
Forward Regenerative
Torque Limit
0 to 300 200% − A −
4A9
L7-04
Reverse Regenerative Torque
Limit
0 to 300 200% − A −
4AA
L7-06
Torque Limit Integral Time
Constant
Sets the integral time constant for the torque limit.
5 to 10000 200
ms
− A −
4AC
L7-07
Torque Limit Control Method
Selection during Accel/
Decel
Selects the method of torque limit control during accel/decel.
0: Proportional Control (change to integral controls at fixed
speeds). Use this setting when acceleration to the desired speed
has priority over torque limitation.
1: Integral Control. Use this setting if the torque limitation has
priority.
When torque limit is applied to the motor, accel/decel time
may increase and motor speed may not meet the speed
reference.
0, 1
0
− A −
4C9
L8: Hardware Protection
Use L8 parameters to configure hardware protection functions.
L8-01
Internal Dynamic Braking
Resistor Protection Selection
(ERF type)
Selects the Braking resistor when using a 3% duty cycle
heatsink mounted braking resistor. This parameter does not
enable or disable the braking transistor of the drive.
0: Resistor overheat protection disabled
1: Resistor overheat protection enabled
0, 1
0
A A A
4AD
L8-02
Overheat Alarm Level
When the heatsink temperature exceeds the value set in this
parameter, an Overheat Alarm (oH) will occur.
50 to 130
<3>
A A A
4AE
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
389