6.6 Operator Programming Errors
An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting is
inappropriate.
The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE occurs,
investigate the cause and
Refer to oPE Codes, Causes, and Possible Solutions on page 291
for the appropriate action. When
an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant). This monitor displays the parameter
causing the oPE error.
u
oPE Codes, Causes, and Possible Solutions
Table 6.11 Detailed oPE Codes, Causes, and Possible Solutions
Digital Operator Display
Error Name
oPE01
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Cause
Possible Solution
The drive capacity setting (o2-04) and the
actual capacity of the drive are not the same. Correct the value set to o2-04.
Digital Operator Display
Fault Name
oPE02
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
Cause
Possible Solution
Parameters were set outside the possible
setting range.
Set parameters to the proper values.
Note:
Other errors are given precedence over oPE02 when multiple errors occur at the same time.
Digital Operator Display
Fault Name
oPE03
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-07.
Cause
Possible Solution
• The same function is assigned to two
multi-function inputs.
• Excludes “Not used” and “External Fault.”
• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.
The Up command was set but the Down
command was not, or vice versa (settings 10
vs. 11).
Correctly set functions that need to be enabled in combination with other functions.
The Up 2 command was set but the Down 2
command was not, or vice versa (settings 75
vs. 76).
• Run/Stop command for a 2-Wire sequence
2 was set (H1-
oo
= 42), but forward/
reverse command (H1-
oo
= 43) was not.
• “Drive Enable” is set to multi-function
input S1 or S2 (H1-01 = 6A or H1-02 = 6A).
Correctly set functions that need to be enabled in combination with other functions.
Two of the following functions are set at the
same time:
• Up/Down Command (10 vs. 11)
• Up 2/Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold
(1E)
• Offset Frequency 1, 2, 3 Calculations (44,
45, 46)
• Check if contradictory settings have been assigned to the multi-function input terminals at the same
time.
• Correct setting errors.
The Up/Down command (10, 11) is enabled at
the same time as PID control (b5-01).
Set b5-01 to 0 to disable PID control or disable the Up/Down command.
6.6 Operator Programming Errors
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
291
6
Troubleshooting