B.4 V/f Pattern Default Values
The tables below show the V/f pattern settings default values depending on the control mode (A1-02) and the V/f pattern
selection (E1-03 in V/f Control).
Table B.3 E1-03 V/f Pattern Settings for Drive Capacity: Models BA0001 to BA0010,
2A0001 to 2A0010, and 4A0001 to 4A0005
No.
Unit
V/f Control
OLV
E1-03
−
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120
180
60.0
60.0
E1-05
<1>
V
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
230
230
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
E1-08
<1>
V
16.0
16.0
16.0
16.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
16.0
16.0
16.0
18.4
13.8
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
E1-10
<1>
V
12.0
12.0
12.0
12.0
8.0
9.0
8.0
9.0
12.0
13.0
12.0
15.0
12.0
12.0
12.0
13.8
2.9
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Table B.4 E1-03 V/f Pattern Settings for Drive Capacity: Models BA0012 to BA0018,
2A0012 to 2A0069, and 4A0007 to 4A0038
No.
Unit
V/f Control
OLV
E1-03
−
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120
180
60.0
60.0
E1-05
<1>
V
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
230
230
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
E1-08
<1>
V
14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
16.1
12.7
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
E1-10
<1>
V
7.0
7.0
7.0
7.0
6.0
7.0
6.0
7.0
9.0
11.0
9.0
13.0
7.0
7.0
7.0
7.0
2.3
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.