n
Single Drive Installation
against a closed surface to avoid diverting cooling air around the heatsink.
A
A
B
C
C
Top/Bottom Clearance
Side Clearance
A – 30 mm minimum
B – Airflow direction
C – 100 mm minimum
Figure 2.2 Correct Installation Spacing
Note:
IP20/NEMA Type 1, IP00/Open-Chassis, and IP20/Open-Chassis models require the same amount of space above and below the drive for
installation.
n
Multiple Drive Installation
When installing multiple drives into the same enclosure panel, mount the drives according to
. When mounting
drives with a minimum side-by-side clearance of 2 mm according to
, derating must be considered and parameter
Refer to Parameter List on page 353
2 mm
A
B
B
C
D
C
A – Line up the tops of the drives.
B – 30 mm minimum
C – 100 mm minimum
D – Airflow direction
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
Note:
When installing drives of different heights in the same enclosure panel, the tops of the drives should line up. Leave space between the top
and bottom of stacked drives for cooling fan replacement if required. Using this method, it is possible to replace the cooling fans later.
NOTICE: When mounting IP20/NEMA Type 1 enclosure drives side by side, the top covers of all drives must be removed as shown in
.
Figure 2.4 IP20/NEMA Type 1 Side-by-Side Mounting in Enclosure
2.2 Mechanical Installation
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
39
2
Mechanical Installation