C1-11
Accel/Decel Time Switching
Frequency
Sets the frequency for automatic acceleration/deceleration
switching.
Below set frequency: Accel/Decel Time 4
Above set frequency: Accel/Decel Time 1
The multi-function input “Accel/Decel Time 1” or “Accel/
Decel Time 2” take priority.
0.0 to 400.0
Hz
0.0 Hz A A A
20A
C1-14
<3>
Accel/Decel Rate
Frequency
Sets the base frequency used to calculate acceleration and
deceleration times.
When set to 0.0 Hz, the drive calculates the time required
to accelerate from 0 Hz to E1-04, and decelerate from E1-04
down to 0 Hz (conventional setting).
When set to any other value above 0.0 Hz, the drive
calculates the time required to accelerate from 0 Hz to
C1-14, and to decelerate from C1-14 down to 0 Hz.
0.0 to 400.0
Hz
0.0 Hz A A A
264
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
C2-01
S-Curve Characteristic at
Accel Start
The S-curve can be controlled in the four points shown
below.
Run
command
Output
frequency
Time
C2-01
C2-04
C2-02
C2-03
ON
OFF
S-curve is used to further soften the starting and stopping
ramp. The longer the S-curve time, the softer the starting
and stopping ramp.
0.00 to
10.00
0.20 s
<4>
A A A
20B
C2-02
S-Curve Characteristic at
Accel End
0.00 to 10.0 0.20 s A A A
20C
C2-03
S-Curve Characteristic at
Decel Start
0.00 to 10.0 0.20 s A A A
20D
C2-04
S-Curve Characteristic at
Decel End
0.00 to 10.0 0.00 s A A A
20E
C3: Slip Compensation
Use C3 parameters to configure the slip compensation function.
C3-01
<1>
Slip Compensation Gain
Sets the slip compensation gain. Decides for what amount
the output frequency is boosted in order to compensate the
slip.
Note:
Adjustment is not normally required.
0.0 to 2.5
0.0
<4>
A A −
20F
C3-02
Slip Compensation Primary
Delay Time
Adjusts the slip compensation function delay time.
Decrease the setting when the slip compensation response
is too slow, increase it when the speed is not stable.
Disabled when Simple V/f Control with PG (H6-01 = 3) is
used.
0 to 10000
2000
ms
<4>
A A −
210
C3-03
Slip Compensation Limit
Sets the slip compensation upper limit. Set as a percentage
of motor rated slip (E2-02). Disabled when Simple V/f
Control with PG (H6-01 = 3) is used.
0 to 250
200% A A −
211
C3-04
Slip Compensation Selection
during Regeneration
Selects slip compensation during regenerative operation.
0: Disabled
1: Enabled
Using the Slip Compensation function during regeneration
may require a braking option to handle momentary
increasing regenerative energy.
0, 1
0
A A −
212
C3-05
Output Voltage Limit
Operation Selection
Selects if the motor magnetic flux is reduced during output
voltage saturation.
0: Disabled
1: Enabled
0, 1
0
<4>
− A −
213
C3-18
<10>
Output Voltage Limit Level
Sets the maximum percentage of output voltage reduction
when C3-05 is enabled.
70.0 to
100.0
90.0% − A −
263
C4: Torque Compensation
Use C4 parameters to configure Torque Compensation function.
B.2 Parameter Table