No.
Description
Unit
Default Settings
−
Model
−
BA0006
BA0010
BA0012
BA0018
o2-04
Drive Model Selection
Hex
33
34
35
37
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
HD
0
1
0
1
0
1
0
E2-11
(E4-11,
T1-02)
Motor rated power
kW
0.75
1.1
1.5
2.2
2.2
3.0
3.7
b3-06
Speed Search current 1
−
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed
Search (Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
Energy saving coefficient
−
223.7
169.4
169.4
156.8
156.8
136.4
122.9
C6-02
Carrier frequency
−
4
7
3
7
3
7
3
E2-01
(E4-01, T1-04) Motor rated current
A
3.3
6.2
6.2
8.5
8.5
11.4
14.0
E2-02
(E4-02)
Motor rated slip
Hz
2.5
2.6
2.6
2.9
2.9
2.7
2.73
E2-03
(E4-03)
Motor no-load current
A
1.8
2.8
2.8
3
3
3.7
4.5
E2-05
(E4-05)
Motor line-to-line resistance
Ω
5.156
1.997
1.997
1.601
1.601
1.034
0.771
E2-06
(E4-06)
Motor leakage inductance
%
13.8
18.5
18.5
18.4
18.4
19
19.6
E2-10
(E4-10)
Motor Iron Loss
W
26
53
53
77
77
91
112
E5-01
Motor Code
hex
0003
0003
0005
0005
0006
0006
0008
L2-02
Momentary power loss ride-through
time
s
0.2
0.2
0.3
0.3
0.5
0.5
1.0
L2-03
Momentary power loss Baseblock time
s
0.3
0.4
0.4
0.5
0.5
0.5
0.6
L2-04
Momentary power loss voltage
recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
Uv detection voltage
V dc
160
160
160
160
160
160
160
L3-24
Motor acceleration time
s
0.142
0.142
0.166
0.145
0.145
0.145
0.154
L8-02
Overheat alarm level
°C
105
105
100
100
95
95
100
L8-09
Ground fault selection
−
0
0
0
0
0
0
0
L8-38
Carrier frequency reduction selection
−
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
10
n2-01
Speed Feedback Detection Control
(AFR) Gain
–
1.00
1.00
1.00
1.00
1.00
1.00
1.50
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
410
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual