Table B.6 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No.
Description
Unit
Default Settings
−
Model
−
2A0001
2A0002
2A0004
2A0006
2A0010
o2-04
Drive Model Selection
Hex
60
61
62
63
65
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
0
1
E2-11
(E4-11,
T1-02)
Motor rated power
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
1.5
2.2
b3-06
Speed Search current 1
−
1.0
1.0
1.0
1.0
1.0
1.0
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed
Search (Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
Energy saving coefficient
−
481.7
356.9
356.9
288.2
288.2
223.7
223.7
196.6
169.4
156.8
C6-02
Carrier frequency
−
4
7
4
7
4
7
4
7
3
7
E2-01
(E4-01,
T1-04)
Motor rated current
A
0.6
1.1
1.1
1.9
1.9
3.3
3.3
4.9
6.2
8.5
E2-02
(E4-02)
Motor rated slip
Hz
2.5
2.6
2.6
2.9
2.9
2.5
2.5
2.6
2.6
2.9
E2-03
(E4-03)
Motor no-load current
A
0.4
0.8
0.8
1.2
1.2
1.8
1.8
2.3
2.8
3.0
E2-05
(E4-05)
Motor line-to-line resistance
Ω
35.98
20.56
20.56
9.84
9.842
5.156
5.156
3.577
1.997
1.601
E2-06
(E4-06)
Motor leakage inductance
%
21.6
20.1
20.1
18.2
18.2
13.8
13.8
18.5
18.5
18.4
E2-10
(E4-10)
Motor Iron Loss
W
6
11
11
14
14
26
26
38
53
77
E5-01
Motor Code
hex
FFFF
FFFF
FFFF
FFFF
0002
0002
0003
0003
0005
0005
L2-02
Momentary power loss ride-through
time
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.3
0.3
L2-03
Momentary power loss Baseblock
time
s
0.2
0.2
0.2
0.2
0.2
0.3
0.3
0.4
0.4
0.5
L2-04
Momentary power loss voltage
recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
Uv detection voltage
V dc
190
190
190
190
190
190
190
190
190
190
L3-24
Motor acceleration time
s
0.178
0.178
0.178
0.178
0.178
0.142
0.142
0.142
0.166
0.145
L8-02
Overheat alarm level
°C
110
110
110
110
115
115
100
100
100
100
L8-09
Ground fault selection
−
0
0
0
0
0
0
0
0
0
0
L8-38
Carrier frequency reduction
selection
−
1
1
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
10
10
10
10
n2-01
Speed Feedback Detection Control
(AFR) Gain
–
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
411
B
Parameter List