Setting 38: Drive Enabled
A Drive Enable digital output will reflect the status of a digital input configured as a Drive Enable input (H1-
oo
= 6A). If
the Drive Enable digital input is closed then the Drive Enabled digital output will also close.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours.
Refer to H2-06: Watt Hour Output Unit Selection on page 204
Setting 3C: LOCAL/REMOTE Status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
Description
Open
REMOTE: The selected external reference (b1-01/b1-02 or b1-15/b1-16) is used as frequency reference and Run command source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Refer to b3: Speed Search on page 130
for details on the
Speed Search function.
Setting 3E: PID Feedback Low
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the level
set to b5-13 for longer than the time set to b5-14.
Refer to PID Feedback Loss Detection on page 141
Setting 3F: PID Feedback High
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the level
set to b5-36 for longer than the time set to b5-37.
Refer to PID Feedback Loss Detection on page 141
Setting 4A: During KEB Operation
Output terminal closes while KEB is being performed.
Refer to Kinetic Energy Backup (KEB) Function on page 219
KEB function description.
Setting 4B: During Short Circuit Braking
Closes the output terminal while Short Circuit Braking is being executed.
Setting 4C: During Fast-stop
Output terminal closes when a Fast-stop is being executed.
Setting 4D: oH Pre-Alarm Time Limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat alarm
has not disappeared after ten frequency reduction operation cycles.
Refer to L8-03: Overheat Pre-Alarm Operation
for details.
Setting 4E: Braking Transistor Fault (rr)
The output closes when the internal braking transistor reaches the overheat level.
5.7 H: Terminal Functions