5-25
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
• When [C26: Heat/Cool control] is set to [1: Enabled], the display and setting can
be made.
• When MV
≥
50%, the control is changed to the PID (heat).
• When MV < 50%, the control is changed to the PID (cool).
• When [C27: Heat/Cool] is set to [1: Energy saving], the heat/cool change is
suppressed to indirectly obtain the energy saving effect. However, when [C28:
Heat/Cool control dead zone] is less than 0.0%, the energy saving effect cannot
be obtained.
• How the relationship between the output (heat) and output (cool) is made for the
PID control result (MV) is set.
Constants oL and oH function as shown in the Figure below.
100.0%
0.0%
Heat MV
100.0%
Cool MV
0.0%
0.0%
50.0%
100.0% MV
100.0%
0.0%
Heat MV
100.0%
Cool MV
0.0%
0.0%
50.0%
Dead zone
Dead zone > 0.0%
Dead zone = 0.0%
100.0% MV
100.0%
0.0%
Heat MV
100.0%
Cool MV
0.0%
0.0%
50.0%
Absolute value of
dead zone
Dead zone < 0.0%
100.0% MV
100%
100%
0%
Cool
MV
Heat
MV
MV
oH
(cool)
oL
(cool)
oL
(heat)
oH
(heat)
Note: A bold line indicates
Heat MV and a dotted
line indicates Cool MV.
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......