RSP input calibration
(1) Select the
[PV Calibration]
tab.
(2) Select the model
[7: C35/36 RSP]
.
(3) Select the gain No. in the ascending order and perform the operation from
step (4).
(4) Click
[Read]
.
(5) Apply the voltage and current values written next to the gain No. to the PV
input terminal.
For details about how to connect measuring instruments in the apply status, refer
to the following Figures:
(6) Keep the apply status for approximately 30s.
(7) Click
[Write]
.
(8) Return to step (3) and repeat the procedure until the final gain No. is
completed.
Handling Precautions
• In the RSP input calibration, it is always necessary to adjust all gains.
• Do not leave the RSP input terminal open during heat-up between
power ON of this unit and starting of calibration. When the input type
is DC voltage, put the unit in the 0 volt input (or terminals are short-
circuited) status.
11-4
Chapter 11. CALIBRATION
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......