5-88
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 12
Current Transformer (CT) Input
For CT input, two kinds of current values are provided.
• Current value at output ON: This current value is used for the heater burnout/over-current event. This current
value is displayed as CT current value.
• Current value at output OFF: This current value is used for the heater short-circuit event. This current value
cannot be displayed.
When [CT type] is set at “heater burnout detection” (C36 = 0 or C39 = 0), the following operation is performed:
The current value at output ON becomes the CT current value measured when the output specified in [CT output]
is turned ON.
The current value at output OFF becomes the CT current value measured when the output specified in [CT output]
is turned OFF.
When [CT type] is set at “current value measurement” (C36 = 1 or C39 = 1), the following operation is performed:
The current value at output ON becomes the measured CT current value regardless of the output ON/OFF status.
The current value at output OFF is fixed at “0.0A”.
The following shows the functional block diagram of the current transformer (CT) input:
Handling Precautions
• The current value at output ON is used when the operation type of the
Internal Event is set at [heater burnout/over-current].
The current value at output OFF is used when the operation type of the
Internal Event is set at [heater short-circuit].
• If a change in current value is 2.5A or less, the CT input suppresses this
change through the filter process.
This prevents the heater burnout event from malfunctioning due to
fluctuation of the current value by variations in heater power voltage.
If the heater current is 2.5A or less, the filter process is activated when
this unit is powered ON or the heater is powered ON. Therefore, it takes
3 to 5s that the heater current becomes equivalent to the actual current
value.
When setting the heater burnout event is set at such low current level, an
ON delay of 3 to 5s is set so that the event is not turned ON accidentally.
(Setting: Setup C36, C39)
Current value at output ON
Current value at output OFF
Current value at output ON.
Current value at
output OFF = 0A
CT type
(Setting: Setup C37, C40)
Monitoring of output status
(ON/OFF)
(Setting: Setup C38, C41)
Wait before measurement
Operation: Heater burnout detection
Output is ON.
Output is OFF.
Operation: Current value measurement
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......