6-11
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
■
Extended tuning bank
Bank selection:
■
Zone bank
Bank selection:
Display
Item
Contents
Initial
value
User
level
Remarks
AT type
0: Normal (Standard control
characteristics)
1: Immediate response (Control
characteristics that respond
immediately to external
disturbance.)
2: Stable (Control characteristics having
less up/down fluctuation of PV)
1
0
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0).
The initial value of “At-d” is
“0.00” when the control
output type is R1.
The initial value of “At-d” is
“1.00” when the control
output type is other than R1.
Just-FiTTER settling
band
0.00 to 10.00
0.30
2
SP lag constant
0.0 to 999.9
0.0
2
AT Proportional band
adjust
0.00 to 99.99
1.00
2
AT Integral time
adjust
0.00 to 99.99
1.00
2
AT Derivative time
adjust
0.00 to 99.99
1.00
or
0.00
2
Control algorithm
0: PID (Conventional PID)
1: RationaLOOP
(High-performance PID)
0
1
Just-FiTTER
overshoot
limit/restraint/control
coefficient
0 to 100
0
1
Display
Item
Contents
Initial
value
User
level
Remarks
Zone 1
-1999 to +9999U
9999U
2
Displayed when the zone
PID operation is used
(C24
≠
0).
Zone 2
9999U
2
Zone 3
9999U
2
Zone 4
9999U
2
Zone 5
9999U
2
Zone 6
9999U
2
Zone 7
9999U
2
Zone hysteresis
5U
2
0 to 9999
Display
Item
Contents
Initial
value
User
level
Remarks
Time proportional
cycle mode
0: Controllability aiming type
1: Actuator service life aiming type
(Only one ON/OFF operation within
time proportional cycle)
0
or
1
2
The initial value is “1” when
control output 1 is the relay
output. The initial value is “0”
in other cases.
SP ramp-up
0.0 to 999.9U
(No ramp when set at “0.0U”)
0.0
2
Time unit of the ramp is
selected by the SP ramp unit
(C32). Displayed when the
SP ramp type is set at
“standard” (C31=0).
SP ramp-down
0.0
2
Output variation limit
0.0: No limit.
0.1 to 999.9%/s
0.0
2
Not displayed when the
model provides the motor
drive relay output and
[aiming at service life of
potentiometer] is set
(C59=1).
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......