![Yamatake SDC35 Скачать руководство пользователя страница 159](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228159.webp)
5-101
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
■
User Function
Up to eight settings selected from various settings can be added to the operation
display.
• Only settings which can be displayed can be registered. (For example, manual
reset of the PID constant can be registered only if integral time (I) is set at 0.)
• Setting cannot be made from the console by using a parameter number displayed
on the setup screen of the
SLP-C35
Smart Loader Package.
• The following keys can be used to select a parameter to be set:
[<]
key:
Moves to the top parameter of the next parameter bank.
[ ]
key:
Displays the next parameter.
[ ]
key:
Displays the previous parameter.
[enter]
key: Executes the start and confirmation of a setting change.
• When using the
SLP-C35
Smart Loader Package, [User Function] can be
registered even though the conditions for instrument status are set as display
disabled.
Handling Precautions
Settings registered as user functions are displayed as if the user level
is High function, in spite of the actual user level setting in setup C79.
Otherwise the display is according to the C79 setting.
<
<
Item (Bank)
Display
Contents
Initial value
User level
User Function 1
(User Function bank)
Each setting is set on the upper display.
The following shows the setting exceptions:
----
: Not registered.
P-_
: Proportional band of currently used
PID group
I-_
: Integral time of currently used PID
group
d-_
: Derivative time of currently used
PID group
rE-_
: Manual reset of currently used PID
group
OL-_
: Output low limit of currently used
PID
OH-_
: Output high limit of currently used
PID group
P-_C
: Proportional band for cool side of
currently used PID group
I-_C
: Integration time for cool side of
currently used PID group
d-_C
: Derivative time for cool side of
currently used PID group
Ol._C
: Output low limit for cool side of
currently used PID group
OH._C
: Output high limit for cool side of
currently used PID group
----
Standard,
High function
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......