• Items marked
●
in the tables are displayed in standard and/or high function configuration.
• To change a user level, refer to
in the lower right part of this page.
Changing the user level
[Instrument information bank]
If necessary, press
[mode] once to
change to the
operation display.
Next, press and
hold [para] for more
than 2 seconds to
get the parameter
setup display.
MOde
flashes on the upper
display.
Press [ ] or [ ]
repeatedly as need-
ed to get
STUP
flashing on the
upper display.
Press [enter].
C0
1
is shown on the
upper display.
Press [<], [ ] or [ ]
to change to
C79
(
user level
).
When [enter] is
pressed, the lower
display flashes.
Press [ ] or [ ] to
change to the desired
setting, and press
[enter] to finalize
your selection.
<
<
<
<
<
<
0: Simple configuration
1: Standard configuration
(initial value)
2: High function configu-
ration
I d
Changing the user level
This controller's user level can be set to 1 of 3 types in setup C79.
The number of possible displays and settings decreases
according to the user level: high function > standard > sim-
ple. All items are displayed when high function is selected.
Display
Item
Contents
Initial value Setting value
I d0 1
●
ROM ID
2: Fixed
Disabled
I d02
●
ROM Version 1
XX. XX (2 digits after decimal point)
Disabled
I d03
●
ROM Version 2
XX. XX (2 digits after decimal point)
Disabled
I d04
●
Loader information
Disabled
I d05
●
EST information
Disabled
I d06
●
Manufacturing date code
Subtract 2000 from the year.
Disabled
(year)
Example: "3" means the year 2003.
I d07
●
Manufacturing date code
Month + day divided by 100.
Disabled
(month, day)
Example: "12.01" means the 1st day of December.
I d08
●
Serial No.
Disabled
[Lock bank]
LOC
Display
Item
Contents
Initial value Setting value
LOC
Key lock
0: All settings are possible
0
1: Mode, event, operation display, SP, UF, lock,
manual MV can be set
2: Operation display, SP, UF, lock,
manual MV can be set
3: UF, lock, manual MV can be set
C.LOC
●
Communication lock
0: read/write enabled 1: read/write disabled
0
L.LOC
●
Loader lock
0: read/write enabled 1: read/write disabled
0
PASS
Password display
0 to 15(5: Password 1A to 2B display)
0
PS 1A
Password 1A
0000 to FFFF (Hexadecimal value)
0000
PS2A
Password 2A
0000 to FFFF (Hexadecimal value)
0000
PS 1b
Password 1B
0000 to FFFF (Hexadecimal value)
0000
PS2b
Password 2B
0000 to FFFF (Hexadecimal value)
0000
[Event configuration bank]
EvCF
Display
Item
Contents
Initial value Setting value
E 1.C 1
to
E8.C 1
Internal event 1 to 8 Configuration 1 Refer to event type (see page 8)
0
Operation type
E 1.C2
to
E8.C2
Internal event 1 to 8 Configuration 2 The digits are determined to 1st, 2nd, 3rd,
Operation type
and 4th digit from the right end.
1st digit: Direct/Reverse
0: Direct 1: Reverse
0
2nd digit: Standby
0: None 1: Standby 2: S Standby at SP change
0
3rd digit: EVENT state at READY
0: Continue 1: Forced OFF
0
4th digit: Undefined
0
0
E 1.C3
to
E8.C3
●
Internal event 1 to 8 Configuration 3 The digits are determined to 1st, 2nd, 3rd,
and 4th digit from the right end.
1st digit: Controller alarm OR
0: None 1: Alarm OR operation
0
2: Alarm AND operation
3: Alarm r OR operation
4: Alarm r AND operation
2nd digit: Special OFF setup
0: As usual
0
1: When the event set value (main setting)
is 0, the event is "OFF".
3rd digit: Delay unit
0: 0.1s 1: 1s 2: 1min
0
4th digit: Undefined
0
0
[DI assignment bank]
Display
Item
Contents
Initial value Setting value
di 1. 1
to
dI 5. 1
Internal contact 1 to 5
0: No function 1: LSP group selection (0/+1)
0
Operation type
2: LSP group selection (0/+2)
3: LSP group selection (0/+4)
4: PID group selection (0/+1)
5: PID group selection (0/+2)
6: PID group selection (0/+4)
7: RUN/READY selection
8: AUTO/MANUAL selection
9: LSP/RSP selection 10: AT Stop/Start
11: Invalid 12: Control action direct/reverse
13: SP Ramp enabled/disabled
14: PV Hold 15: PV Maximum value hold
16: PV Minimum value hold 17: Timer Stop/Start
18: Release all DO latches (Continue/Release)
19: Advance 20: Invalid
dI 1.2
to
dI 5.2
●
Internal contact 1 to 5
0: Not used (Default input)
0
Input bit function
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)
dI 1.3
to
dI 5.3
●
Internal contact 1 to 5
0: Normally opened 1: Normally closed
2: Contact 1
Input assign A
2 to 5: DI1 to 4 6 to 9: Undefined
3: Contact 2
10 to 17: Internal Event 1 to 8
4: Contact 3
18 to 21: Communication DI1 to 4
5: Contact 4
dI 1.4
to
dI 5.4
●
Internal contact 1 to 5
22: MANUAL 23: READY 24: RSP
0
Input assign B
25: AT running 26: During SP ramp 27: Undefined
dI 1.5
to
dI 5.5
●
Internal contact 1 to 5
28: Alarm occurs 29: PV alarm occurs
0
Input assign C
30: Undefined 31: mode key pressing status
dI 1.6
to
dI 5.6
●
Internal contact 1 to 5
32: Event output 1 status
0
Input assign D
33: Control output 1 status
dI 1.7
to
dI 5.7
●
Internal contact 1 to 5
The digits are determined to 1st, 2nd, 3rd
Polarity A to D
and 4th digit from the right end.
1st digit: Polarity A
0: Direct 1: Reverse
0
2nd digit: Polarity B
0
3rd digit: Polarity C
0
4th digit: Polarity D
0
dI 1.8
to
dI 5.8
●
Internal contact 1 to 5 Polarity
0: Direct 1: Reverse
0
dI 1.9
to
dI 5.9
●
Internal contact 1 to 5
0: Every Internal Event
0
Event channel def.
1 to 8: Internal Event No.
di
[DO assignment bank]
Display
Item
Contents
Initial value Setting value
Ot 1. 1
to
Ot2. 1
●
Operation type (Control output 1 to 2, 0: Default output 1 to 2: MV1 to 2
0
Ev 1. 1
to
Ev3. 1
Event output 1 to 3)
3 to 6: Function 1 to 4
Ot 1.2
to
Ot2.2
●
Output assign A (Control output 1 to 2, 0: Normally opened 1: Normally closed
14: Output 1
Ev 1.2
to
Ev3.2
Event output 1 to 3)
2 to 9: Internal Event 1 to 8
15: Output 2
10 to 13: Undefined 14 to 15: MV1 to 2
2: Event 1
16 to 17: Undefined 18 to 21: DI1 to 4
3: Event 2
22 to 25: Undefined
4: Event 3
Ot 1.3
to
Ot2.3
●
Output assign B (Control output 1 to 2, 26 to 30: Internal Contact 1 to 5
0
Ev 1.3
to
Ev3.3
Event output 1 to 3)
31 to 33: Undefined 34 to 37: DI1 to 4
38: MANUAL 39: READY 40: RSP
Ot 1.4
to
Ot2.4
●
Output assign C (Control output 1 to 2, 41: AT running 42: During SP ramp 43: Undefined
0
Ev 1.4
to
Ev3.4
Event output 1 to 3)
44: Alarm occurs 45: PV alarm occurs
46: Undefined 47: Mode key pressing status
Ot 1.5
to
Ot2.5
●
Output assign D (Control output 1 to 2, 48: Event output 1 status
0
Ev 1.5
to
Ev3.5
Event output 1 to 3)
49: Control output 1 status
Ot 1.6
to
Ot2.6
●
Control output 1 to 2, Event output
The digits are determined to 1st, 2nd, 3rd,
Ev 1.6
to
Ev3.6
1to 3 Polarity A to D
and 4 th digit from the right end.
1st digit: Polarity A
0: Direct 1: Reverse
0
2nd digit: Polarity B
0
3rd digit: Polarity C
0
4th digit: Polarity D
0
Ot 1.7
to
Ot2.7
●
Polarity (Control output 1 to 2,
0: Direct 1: Reverse
0
Ev 1.7
to
Ev3.7
Event output 1 to 3)
Ot 1.8
to
Ot2.8
●
Latch (Control output 1 to 2,
0: None 1: Latch (Latch at ON)
0
Ev 1.8
to
Ev3.8
Event output 1 to 3)
2: Latch (Latch at OFF except for initialization
at power ON)
dO
Key operation • display
[User function bank]
Display
Item
Contents
Initial value Setting value
UF- 1
to
UF-8
●
User function 1 to 8
–
–
UF
Display
Item
Contents
Initial value
Setting value
C75
MV display setup
Bit 0: MV display (Enabled: +1)
15
(Sum of the weighting)
Bit 1: Heat MV/cool MV display (Enabled: +2)
Bit 2: MFB display (Enabled: +4)
Bit 3: AT progress display (Enabled: +8)
C76
EV display setup
0: Not displayed
0
(Operation display)
1: Set value of Internal event 1 is displayed
2: Set values of Internal event 1 to 2 are displayed
3: Set values of Internal event 1 to 3 are displayed
C77
Timer remain time display setup
0: Not displayed
0
(Operation display)
1: Internal event 1 is displayed
2: Internal event 1 to 2 is displayed
3: Internal event 1 to 3 is displayed
C78
CT display setup
0: Not displayed 1: CT1 current value is displayed
0
(Operation display)
2: CT1 to 2 current values are displayed
C79
User level
0: Simple configuration 1: Standard configuration
1
2: High function configuration
C80
●
Communication monitor
0: Not used
0
display
1: Flashing while data is sending through
RS-485 communication
2: Flashing while data is receiving through
RS-485 communication
3: Logical OR of all DI statuses
4: Flashing in READY mode
C81
●
MS display, Condition
0: Normally OFF 1: Normally ON
39
(top priority)
2 to 9: Internal event 1 to 8
10 to 13: Undefined 14: MV1 15: MV2
16 to 17: Undefined 18 to 21: DI1 to 4
22 to 25: Undefined
26 to 30: Internal contact 1 to 5
31 to 33: Undefined
34 to 37: Communication DI 1 to 4
38: MANUAL 39: READY 40: RSP
41: AT 42: During ramp 43: Undefined
44: Alarm 45: PV alarm 46: Undefined
47: [mode] key pressing status
48: Event output 1 terminal status
49: Control output 1 terminal status
C82
●
MS display, Status
0: lit 1: Slow flashing 2: Flashing twice
1
(top priority)
3: Fast flashing 4: Left to right
5: Right to left
6: Reciprocating between left and right
7: Deviation OK 8: Deviation graph
9: MV graph 10: Heat-side MV graph
11: Cool-side MV graph 12: MFB graph
13: DI monitor 14: Internal contact monitor
15: Internal event monitor
C83
●
MS display, Condition
Same as MS display, Condition (top
44
(secondary priority)
priority)
C84
●
MS display, Status
Same as MS display, Status (top priority)
6
(secondary priority)
C85
●
MS display, Condition
Same as MS display, Condition (top
1
(third priority)
priority)
C86
●
MS display, Status
Same as MS display, Status (top priority)
9
(third priority)
C87
●
MS display, Deviation range
0 to 9999U
5
C88
●
Special function
0 to 15 (This value becomes "0" when the
0
power is turned ON.)
C89
●
Zener barrier adjustment
The value can be changed with the adjustment
0.00
The numeric value cannot be directly
input with the manual operation.
C90
●
Number of CT1 turns
0: 800 turns 1 to 40: CT turns divided by 100
8
C9 1
●
Number of CT1 power wire loops
0: 1 time 1 to 6: Number of times
1
C92
●
Number of CT2 turns
0: 800 turns 1 to 40: CT turns divided by 100
8
C93
●
Number of CT2 power wire loops
0: 1 time 1 to 6: Number of times
1
Precaution for setup
· The type of auto tuning can be changed by changing the value of
At.ty
(AT
type) in the extended tuning bank. Set it to match the control characteristics.
· Be sure the motor is adjusted:
C60
(motor auto adjust: start) in the setup bank.
· The result of AT control on a position proportioning model is that derivative
time (D) = 0. If satisfactory control cannot be obtained, set
At-d
(AT deriva-
tive time adjust, in the extended tuning bank) to 1.00.
D-7
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......