Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
Set value
Direct action
Reverse action
of operation
type
Alarm
23
ON if alarm occurs (alarm code AL01 to 99).
OFF if alarm occurs (alarm code AL01 to 99).
(status)
OFF in other cases.
ON in other cases.
READY
24
ON in the READY mode.
OFF in the READY mode.
(status)
OFF in the RUN mode.
ON in the RUN mode.
MANUAL
25
ON in the MANUAL mode.
OFF in the MANUAL mode.
(status)
OFF in the AUTO mode.
ON in the AUTO mode.
RSP
26
ON in the RSP mode.
OFF in the RSP mode.
(status)
OFF in the LSP mode.
ON in the LSP mode.
During AT
27
ON when AT is executed.
OFF when AT is executed.
(Status)
OFF when AT is stopped.
ON when AT is stopped.
During SP ramp
28
ON during SP ramp.
OFF during SP ramp.
OFF when SP ramp is not performed or is completed. ON when SP ramp is not performed or is completed.
Control action
29
ON during direct action (cooling).
OFF during direct action (cooling).
(status)
OFF during reverse action (heating).
ON during reverse action (heating).
ST setting standby
30
Invalid in this unit. Always OFF.
Invalid in this unit. Always ON.
(status)
During estimated
31
ON during estimated position control.
OFF during estimated position control.
position control
OFF when not estimated.
ON when not estimated.
(status)
Timer
32
(status)
High and low limits
33
of MFB value
The direct and reverse action settings are disabled for the timer event.
When using the timer event, it is necessary to set the operation type of the DI assignment to
"Timer Start/Stop". Additionally, when setting the event channel designation of the DI
assignment, multiple timer events are controlled from individual internal contacts (DI).
●
Setting items
• ON delay time: A period of time necessary for the event change from OFF to ON after DI has
been changed from OFF to ON.
• OFF delay time: A period of time necessary for the event change from ON to OFF after DI
has been changed from ON to OFF.
●
Operation specifications
• The event is turned ON when DI ON continues for ON delay time or longer.
• The event is turned OFF when DI OFF continues for OFF delay time.
• In other cases, the current status is continued.
●
CAUTION
When setting the ON delay and OFF delay, it is necessary to put in "High function
configuration".
The default settings of the ON delay and OFF delay before shipment are 0.0s.
The default setting of the event channel designation of the DI assignment before shipment is
"0". In this case, the timer event start/stop can be set for all internal events from one internal
contact (DI).
Additionally, as one or more event channel designation is set, the timer event start/stop can
be set for one internal event specified by one internal contact (DI).
However, when setting the event channel of the DI assignment, it is necessary to put in "High
function configuration".
Time
ON
Internal event
ON
DI
OFF delay
ON delay
Main setting(*1)
Sub setting(*1)
Main setting(*1) Sub setting(*1)
MFB
MFB
ON
HYS
ON
HYS
ON
HYS
HYS
*1
If the setting is made so that the main setting is greater than the sub setting, the operation is performed with the
main setting swapped for the sub setting automatically.
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......