1. Error Messages
12.32 : DO1 DC24V disconnected
Code
: &H0C20
Meaning/Cause
: a. DC 24V not being supplied to DO1 section of OPT.DIO unit.
b. Drop in DC 24V supply voltage to DO1 section of OPT.DIO unit.
c. OPT.DIO connector is not connected.
Action
: 1. Supply DC 24V to DO1section of OPT.DIO unit.
2. Check for short, breakage or wiring error in OPT.DIO connector.
3. Check if load connected to DO1 section of OPT.DIO unit is
too large for the DC 24V supply to handle.
12.33 : DO2 DC24V disconnected
Code
: &H0C21
Meaning/Cause
: a. DC 24V not being supplied to DO2 section of OPT.DIO unit.
b. Drop in DC 24V supply voltage to DO2 section of OPT.DIO unit.
c. OPT.DIO connector is not connected.
Action
: 1. Supply DC 24V to DO2 section of OPT.DIO unit.
2. Check for short, breakage or wiring error in OPT.DIO connector.
3. Check if load connected to DO2 section of OPT.DIO unit is
too large for the DC 24V supply to handle.
12.34 : POS.OUT Point not exist
Code
: &H0C22
Meaning/Cause
: Comparison point data does not exist.
Action
: Set comparison point data correctly.
12.35 : POS.OUT Point unit error
Code
: &H0C23
Meaning/Cause
: Comparison points 1 and 2 do not use the same unit system.
Action
: Change them to the same unit system.
12.41 : EtherNet link error
Code
: &H0C29
Meaning/Cause
: TELENET is disconnected.
a. The cable is broken or disconnected.
b. Communicating with a client was off for more than the time
specified by the "7. timeout [min]" parameter for EtherNet.
c. Logout was attempted while the 11. logout" parameter for
EtherNet is set to "STOP".
d. No response for a keep-alive packet from the client.
Action
: 1. Connect the cable or connector securely.
2. Communicate with a client at least once within the time
specified by the "7. timeout [min]" parameter, or set the
parameter to "0" to disable the timeout function.
3. Set the "11. logout" parameter to "CONT." to avoid errors
during logout.
4. Check whether the client is responding to the keep-alive
packet, or set the "12. keep-alive [sec]" parameter to "0" to
stop the keep-alive packet from being sent out.
Содержание RCX141
Страница 1: ...User s Manual ENGLISH E YAMAHA 4 AXIS ROBOT CONTROLLER E93 Ver 2 02 RCX141 ...
Страница 2: ......
Страница 16: ...viii MEMO ...
Страница 18: ...MEMO ...
Страница 24: ...1 6 MEMO ...
Страница 26: ...MEMO ...
Страница 34: ...2 8 MEMO ...
Страница 36: ...MEMO ...
Страница 54: ...3 18 MEMO ...
Страница 290: ...4 232 MEMO ...
Страница 292: ...MEMO ...
Страница 316: ...5 24 MEMO ...
Страница 318: ...MEMO ...
Страница 326: ...6 8 MEMO ...
Страница 328: ...MEMO ...
Страница 338: ...7 10 MEMO ...
Страница 340: ...MEMO ...
Страница 346: ...MEMO ...
Страница 401: ...MEMO ...