194
Q10: What is the external connection method and parameter setting of regenerative resistance?
There are P+, D, C terminals on the servo interface. There are short connectors between P+ and C
(using built-in resistor). When the built-in resistor specifications are insufficient, the external resistor
should be replaced. The specifications of the external regenerative resistor please refer to chapter 1.4.1.
(1) P+, D, C interface model: Remove the short joint between P+, D, and connect the external
regenerative resistance to P+, C.
(2) P+, PB interface model: connect external regenerative resistance to P+, PB.
(3) Version number parameter U2-07 < 3700, set P0-24 = 1, P0-25 = power value, P0-26 = resistance
value.
(4) Version number parameter U2-07 ≥ 3700, P0-24 need not be set, P0-25 = power value, P0-26 =
resistance value.
Note: Before 3700 version, P0-24 should be set. Value 0 is for built-in resistance and value 1 is for
external resistance.
Q11: The service life of tank chain?
The bending resistance is 5 million times and the bending radius is 50 mm.
Q12: How to connect bus control BD board and JA-NE-L?
A-A1, B-B1, SG-SG when one axis running; the PLC BD board and the terminal resistor of the last
JA-NE-L board of electrical connection should be ON when multi-axis running; and the terminal
resistance of JA-NE-L board in the middle should be OFF.
Содержание DS5F Series
Страница 1: ...DS5F series servo driver User manual WUXI XINJE ELECTRIC CO LTD Data No SC5 02 20200217 2 3 ...
Страница 2: ......
Страница 41: ...39 3 2 5 Encoder feedback output signal Servo driver differential to collector upper device ...
Страница 124: ...122 2 select jog setting or manual setting to configure the inertia estimation trip 3 Set the auto tuning interface ...
Страница 202: ...200 Appendix 9 Torque speed characteristic curve ...
Страница 203: ...201 ...
Страница 204: ...202 ...