160
31
0
E-310
Power mismatch
between
driver
and motor
Such as 750W driver
with 200W motor
Match the correct motor and
driver, and use it after setting the
P0-33 motor code correctly
31
1
E-311
When the motor
code
is
read
automatically,
the
motor
parameter is 0,
and the driver
P0-33 = 0
Motor code not set
On the premise that the driver and
motor are matched and can be
used together, read the alarm
shielding
position
of
motor
parameters through P0-53, and set
the motor code of P0-33 correctly
2
E-312
Reading
motor
parameter
is
damaged
Parameter
CRC
verification failed
On the premise that the driver and
motor are matched and can be
used together, read the alarm
shielding
position
of
motor
parameters through P0-53, and set
the motor code of P0-33 correctly
3
E-313
Encoder software
version mismatch
Encoder
software
version mismatch
①
Update driver firmware to
maximize current motor parameter
performance
②
Read the alarm shielding
position of motor parameters
through p0-53, and set the motor
code of P0-33 correctly. At this
time, the motor parameters are in
the driver, which can work
normally, but may affect some
performance
4
E-314
Motor code does
not
match
software version
Encoder
hardware
version is higher than
driver firmware version
Contact
the
manufacturer's
technical support to update the
driver firmware
5
E-315
When the motor
code
is
read
automatically,
the
motor
parameter is 0,
and the driver
P0-33
≠
0
Read the motor code is 0
On the premise that the driver and
motor are matched and can be
used together, read the alarm
shielding
position
of
motor
parameters through P0-53, and set
the motor code of P0-33 correctly
6
E-316
Auto-read
code
error
The auto read motor
code is inconsistent with
the motor code set in
P0-33
Check U3-00 and motor label.
①
If the two values are the same,
change P0-33 motor code or set
P0-33 to 0 to read motor code
automatically;
②
If the two values are different,
contact the manufacturer for
technical support
Содержание DS5F Series
Страница 1: ...DS5F series servo driver User manual WUXI XINJE ELECTRIC CO LTD Data No SC5 02 20200217 2 3 ...
Страница 2: ......
Страница 41: ...39 3 2 5 Encoder feedback output signal Servo driver differential to collector upper device ...
Страница 124: ...122 2 select jog setting or manual setting to configure the inertia estimation trip 3 Set the auto tuning interface ...
Страница 202: ...200 Appendix 9 Torque speed characteristic curve ...
Страница 203: ...201 ...
Страница 204: ...202 ...