Fan - CI152TF/S
Fan control is determined by the temperature on the heat sink.
•
A very high power request, such as two elements on 100% or one on boost switches the fans on independ-
•
ently of the heatsink temperature.
After generator is off, fan continues to run until heat sink temperature is below 113° F, or up to 600 seconds.
•
Fan is limited to low speed when the generator is off.
•
Temperature thresholds:
113° F - start low speed
•
131° F - start high speed
•
Fan - TM15TF/S
Fan control is determined by the temperature on the heat sink.
•
A very high power request, such as both elements on 100% switches the fan on independently of the
•
heatsink temperature.
After generator is off, fan continues to run until heat sink temperature is below 113° F, or up to 600 seconds.
•
Fan is limited to low speed when the generator is off.
•
Temperature thresholds:
113° F - start low speed
•
131° F - start high speed
•
Modes
Power Up Mode - All Models
All LED indicators are on for two seconds.
•
Timer digits will indicate the appliance type ‘SS’ for SM15TF/S, ‘FF’ for FM15TF/S, and ‘LL’ for GM15TF/S. The
•
control will default to SM15TF/S if the appliance type cannot be determined due to an EEPROM issue or if the
EEPROM is not programed.
After LED power up sequence the annunciator sounds the Acceptance beep.
•
During the Acceptance beep the unit enters Lock Mode.
•
LOCK
display is on.
•