2.1 Scope of supply. packaging
Boiler covered with a plastic sack.
The cladding. control panel and small parts can be found in separate cardboard boxes and in the filler chamber.
Fig. 2
LogWIN Premium Touch boiler
Fig. 3
Cardboard boxes with cladding and
control panel
2.2 System
2.2.1 Area of use
For heating buildings acc. to EN 12831.
The boilers are designed and approved as heat generators for hot water heating systems with permissible flow tem-
peratures of up to 90 °C. They may be installed only in sealed systems. The max. boiler temperature for the LogWIN is
limited in the factory to 80 °C.
The resulting flow temperature depends on the relevant operating status and the line losses to the system.
2.2.2 Standards
The following European Standard should be followed: EN 12828. according to this the following should be fitted:
a) A closed expansion tank.
b) A reliably functioning safety valve (with max. 3 bar reaction pressure) installed at the highest point of the boiler or
at a non-closable line.
c) A thermometer. a pressure gauge.
d) An automatic device for dissipating heat which will prevent the maximum water temperature in the boiler of 110 °C
from being exceeded. The built-in thermal safety device (heat exchanger) should always be used with the thermal
discharge safeguard.
e) A low-water cut-off: A low-water cut-off is not required for systems providing up to 300 kW nominal thermal output.
if it can be ensured that a lack of water in the system will not result in excess heating.
If the boiler is above the radiators. then a low-water cut-off must be installed.