3.
For the electrician
– Remove the 2 screws at the front of the control panel and open the cover – Fig. 86.
Fig. 86 Removing the 2 screws. opening the cover
– Make sure that the plugs for the door switch. flue gas sensor X11 (accessories) and air control X6/X7. X14 are correct-
ly connected in the control panel. Cables and plugs are inscribed – Fig. 87.
CAUTION
Be sure to note the separate wiring of the extra-low voltage line (0–12 V DC) and
low-voltage line (230 V AC)! Route cables in the cable channels available – Fig. 87.
Fig. 87 Control panel open. connecting plugs – front view
Cable channel
Extra-low voltage
(0–12 V DC)
Cable channel
Low voltage
(230 V AC)
Air control
Plug X14
Air control plug
X6/X7
Flue gas sensor
(accessories)
Plug X11
Door switch
plug X15
– Connecting automatic ignition (accessories)
See separate installation instructions provided.
CAUTION
Electrical cables should be routed in the cable channels intended for this purpose and
are not allowed to be routed over the cleaning cover. The space above the cover must
be accessible for cleaning.
CAUTION
After connecting the cables. remove all remaining assembly materials (e.g. wire
strands) from the control panel.