ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 68
Profiler Option
59407, Issue 3 – May 2011
10 The Profiler Option
The features covered in this section are only available on models fitted with the Profiler
(Setpoint Programmer) option. If the instrument also has the Data Recorder option fitted, it’s
Real Time Clock is used to expand the profiling capabilities by adding Day & Time profile
start options, releasing of hold segments at a specific time of day and changing the power fail
recovery option to one based on the length of time the power has been off. These features
are explained below and in the Profiler Setup and Profile Control menus (refer to section 7)
Introduction
The Profiler option allows the user to store up to 255 profile segments, shared between a
maximum of 64 Profiles. Each profile controls the value of the setpoint over time; increasing,
decreasing or holding its value as required. If fitted, Profiler options are added to the Main
Menu as well as the Operation Mode.
Profiler Enabling
Controllers supplied without the Profiler option installed can be upgraded in the field by
purchasing a licence code number from your supplier. Refer to the Field Upgrade information
(
Section 3
) for more details.
Profile Components
The General Profile Configuration settings decide how profiles can be Run, Held or Aborted.
These settings apply to all profiles.
Each profile has its own header information, plus 1 or more segments.
Profile Header & Segment Information
The profile header contains information about how the profile starts and stops, the power
loss recovery action and how many times it should be repeated.
Note:
Profile Header information is stored to memory as the Segment creation sequence begins.
No profile is created if you exit before this point.
Segments can be ramps, dwells, steps or special segments such as holds, ends or joins.
Note: Segment information is stored as each segment is created, but the profile remains
invalid until an end or join segment is defined.